User Manual

en_BA_U500_UR18_Gen2_IO-Link.docx 15/43 Baumer Electric AG
04.04.2019/ Frauenfeld, Switzerland
4.3.2.3 Hysteresis Width
The hysteresis is configured in percent of the switch point distance. It is the difference between switch point
and reset point (see Figure 11). This parameter can be beneficial to smoothen out signals when samples
have quickly changing positions.
Figure 11 Hysteresis is the difference between switch point and reset point
- Bright blue: object moving from far to close distance (in this case switch point)
- Dark blue: moving from close to far distance (in this case reset point)
Parameter name
Short Description
Rights
Unit / Allowed values
Hysteresis.SSC1 Width
Adjust hysteresis width as percent
of the switch point distance
rw
Limits 0 … 99 %, Default 4%
4.3.2.4 Hysteresis Alignment Mode
In case of axial detection tasks like stop trigger or level detection, an accurate switching distance is required.
To adapt the switching behavior and the hysteresis to the movement direction of the object, the alignment of
the hysteresis can be changed.
Hysteresis settings are available for .P, D and .R types.
Parameter name
Short Description
Rights
Unit / Allowed values
SSC1 Config.Hyst
Selects the hysteresis alignment
mode
rw
- Left Aligned
- Center Aligned
- Right Aligned (Default)