Manual

BG1100M Direct Spark Ignition Control Installation Instructions 5
Table 1: LED Indications During Normal Operation
Flash Code Flash Code Indication
Steady On Flame detected, burner on
.50 Second On
.50 Second Off
Prepurge period
.10 Second On
.10 Second Off
Trial time, spark on
.25 Second On
1.0 Second Off
Trial time
Troubleshooting
If the system does not function properly, determine the
cause using the procedures in this section.
Before proceeding with troubleshooting the system, check
the following.
Preliminary Checks
Are you using resistive wire between the module spark
(10) and the pilot connection?
Are all mechanical and electrical connections tight?
Is the system wired and ground correctly?
Is gas inlet pressure per manufacturer’s specifications?
Is the system powered?
Is the thermostat calling for heat?
!
WARNING: Risk of Personal Injury. Do not place
face, hands, or other parts of the body in or near the
burner area when the LED is flashing (recycle mode).
When the LED is flashing, the control may at any time
(while in the recycle mode) re-energize the burner control
system and ignite the burner which may result in electric
shock from contact with the electrode or severe burn injury
from firing of the burner.