Product Overview
Y71/GM-70 Regulator Conversion Kits Product Bulletin 3
Technical Specifications
Product
Y71/GM-70 Conversion Kits
Lever-Acting Regulator: 3 to 6 in. W.C. (7.5 to 15 mbar)
6 to 12 in. W.C. (15 to 30 mbar)
Direct-Acting Regulator: 3 to 6 in. W.C. (7.5 to 15 mbar)
8 to 12 in. W.C. (20 to 30 mbar)
Conversion Kit Range of
Regulation
Direct-Acting GM-7xxx Regulator: 3 to 5 in. W.C. (7.5 to 12.5 mbar)
9 to 12 in. W.C.(22.5 to 30 mbar)
Natural Gas: 0.019 in. (0.48 mm) leak-limiting diameter
Conversion Kit Seal Screw
Liquefied Petroleum (LP) 0.016 in. (0.41 mm) leak-limiting diameter
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult BASO Gas Products. BASO Gas Products shall not be liable for damages resulting from misapplication or misuse of its
products.
Refer to the Y71 Regulator Conversion Kits Technical Bulletin (LIT-121805), Y71AA Conversion Kit Installation Instructions
(Part No. 24-8711-617), GM-70-CLP Regulator Conversion Kit Installation Instructions (Part No. 24-8711-757), GM-70-CBP Conversion Kit
Installation Instructions (Part No. 24-8711-811), and GM-70-CNG Regulator Conversion Kit Installation Instructions (Part No. 24-8711-862) for
necessary information on the installation, use, and servicing of this product.
1007 South 12th Street
PO Box 170
Watertown, WI 53094 www.baso.com
1-877-227-6427 (1-877-BASOGAS) Published in U.S.A.