Install Instructions
Installation Instructions H91 Model Rev. B
Issue Date July 27, 2018
H91 Model Rev. B Series Shutoff Gas Valve
© 2018 BASO Gas Products 1
Part No. BASO-INS-H91MODELREVB, Rev.- www.baso.com
H91 Model Rev. B Series Shutoff Gas Valve
Applications
The H91 Series shutoff gas valve is an electrically
operated gas valve that will open on a demand signal
from a thermostat or other controlling device and
automatically close when the signal is removed.
Typical applications include heaters, wall furnaces,
commercial cooking equipment, roof top makeup units
and similar applications. The H91 Series can be used
with natural gas and LP gas at pressures up to 0.5 psi.
Its compact size permits installation in space restrictive
applications.
Installation
IMPORTANT: Only qualified personnel should
install or service BASO
®
Gas Products. These
instructions are a guide for such personnel. Carefully
follow all instructions in this document and all
instructions for the appliance.
IMPORTANT: Make all gas installations in
accordance with applicable local, national, and
regional regulations.
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the H91 Series.
Failure to shut off the gas supply can result in the
release of gas during installation or servicing, which
can lead to an explosion or fire, and may result in
severe personal injury or death.
!
WARNING: Risk of Explosion, Fire, or
Electric Shock. Label all wires before they are
disconnected when replacing or servicing the
H91 Series. Wiring errors can cause improper or
dangerous operation and may result in an explosion,
fire, or electric shock leading to severe personal
injury or death.
IMPORTANT: Verify that the valve is installed
only in applications where the specified maximum
ambient (surface) temperature and maximum
operating pressure does not exceed the limits in the
Technical Specifications section.
To install the H91 Series valve:
1. Shut off power to the appliance.
2. Shut off the gas at the main manual shutoff valve.
3. Label each wire with the correct terminal
designation prior to disconnection.
4. Compare the voltage on the valve with the power
source voltage to ensure the correct unit is being
installed. For valves with 25-volt coils, use a
National Electrical Code (NEC), Class 2
transformer.
Note: The transformer must be mounted to a
grounded metal enclosure.
5. Ensure that the gas flows through the valve body
in the direction indicated by the “IN” and “OUT” or
by the arrow on the valve body. If the valve is
installed with the gas flow in the opposite
direction, leakage can occur.
IMPORTANT: Do not use a wrench on any
surface other than the casting flats provided at the
inlet and outlet ends of the valve body.
The H91 Series may be damaged in the mounting
process if a wrench is used on any other surface.
Using a wrench incorrectly may void the warranty.