User Manual
BaselineInc. 19
Er5isdisplayed
(PressRead/Setto
clearthiswarning
message.)
Unexpectedreading
during24‐hourauto
calibraon–finalreading
wasnotsubstanally
differentfromthefirst.
Makesurenoextrawateris
appliedtothebiSensoraer
autocalibraonstartsorthe
S100maysetaunacceptable
threshold.
Er6isdisplayed Unexpectedlowreading
duringthe24‐hourauto
calibraon.
Ensuresoiliscompactedaround
sensorwithnotairpocketsor
rockstouching.
Re‐saturatesoil,andthenre‐run
the24–hourautocalibraon.
Displayisblank
LEDsareoff
S100isnotreceiving24
VAC.
Makesurethe24VAC
transformerispluggedinand
receivingpower
Ensurethe24VACwireand
commonwirefromtheS100are
properlyconnected.
biSensorisreading
avalueunder20
Soilappearswet
Theremaybeairpockets
aroundthebiSensor.
Re‐burythebiSensor.
BeespeciallycarefulthatNO
rocksaretouchingthebladeof
thesensorasthiscanleadto
falsereadings.
Controllerdoes
nothaveaccessto
24VAC
Someoldermechanical
controllersdonothave
accessto24VAC.
Purchaseandinstalla24VAC
transformer.
Formoreinformaon,contact
Baselinesupportat
866‐294‐5847.
ErrorCodeor
Condition
Status RecommendedAction