User Manual
BaselineInc. 15
Step6–CalibratetheSensor(AutoCalibrationMode)
TheS100hasanAutoCalibraonmodethatrunsfor24hours.Autocalibraonsets
themoisturethresholdbasedonyoursoiltype.Thisisimportantfornewinstallaons
andusefulforrecalibrangabiSensor.
1. HeavilysaturatethesoilaroundthebiSensorwithwater.Ifthe
soilisnotproperly
saturated,theautocalibraonwillfail.
2. Aerthewaterhassoakedintothesoil,brieflypresstheRead/Setbuononthe
S100totakethecurrentmoisturereading.Writedownthecurrentdate,me,
andmoisturereadingtobeusedas
areferencepoint.
Date:_______________Time:__________MoistureReading:___________
2. Pressandholdthe+,–,andBypassbuonssimultaneouslyfor3seconds.The
displaywillflashbetweenCAL,24H,andthemoisturereading.Thedisplaywill
countdown,onthehour,unlthecalibraoniscomplete.
Wateringisstopped
whiletheS100isinAutoCalibraonmode.DonotallowthebiSensortoreceive
anywaterduringcalibraon.Thisprocesswillfailorprovidefalsefeedbackifit
does.
NotesontheAutoCalibrationProcess
ToexittheAutoCalibraonmode,pressandholdtheRead/Setbuonfor3
seconds.
Ifthecalibraonsucceeds,themoisturethresholdwillbeautomacallyset,and
thesystemwillallowwateringwhensoilmoisturedropsbelowthisthreshold.
Ifanerroroccursduringautocalibraon,thescreenwillflashEr4indicangthat
calibraonfailed.TheEr4codeisfollowedbyanothercodewithanumberthat
correspondstothereasonforfailure.SeetheTroubleshoongseconfor
informaononthevariouserror
messages.
Iftheautocalibraonfails,theS100willwaterbasedonthepreviouslyset
threshold.
IfthebiSensorreceiveswaterduringthe24hourcalibraonperiod,orthesoil
wasnottotallysaturated,thecalibraonwilleitherfailenrelyorsetanincorrect
thresholdforyourlawn.Ifthishappens,youwillneedtore‐saturatethesoiland
restarttheautocalibra
on.
Ifthethresholdsetbytheautocalibraonisunacceptable,trythemanual
calibraonprocessdescribedonthenextpage.