User Manual

WaterTecS100UserManual 10
Step3–ConnectthebiSensor&TestCommunication
TestingCommunication
Pressandholdthe+,,andRead/Setbuonssimultaneouslyfor3seconds,andthen
releasethebuons.
ThecommunicaontestcausesthebiSensortotake100readings.Duringthetest,
whichtakesabout2minutes,thedisplayalternatesbetweenSEnandanumberthat
startsat
100andcountsdownto0.
Whenthetestiscomplete,thedisplayalternatesbetweenErrandanumberfrom000
to200,whichindicatesthenumberoferrors.Areadingof000isgooditindicates
therewerenoerrors.Thiserrorcountstopsdisplayingaer10
minutes.
Note:Donotconfusetheerrorcountwiththeerrortype.
ErrorslikelytooccuratthisstageareEr1,Er2,orEr3.SeetheErrorCodesseconfora
descripon.
Tointerruptthecommunicaontest,pressandholdtheRead/Setbuonfor3
seconds.
ConnectingthebiSensor
1.Determinewhichzone/valveoperatesthesprinklersinthelocaonwherethe
sensorwillbeburied.
Note:ThemaximumallowablewiredistancebetweenthebiSensorandtheS100
unitis500feet.
2.Gototheboxwherethatvalveislocated.
3.Disconnectthevalvewiringinsidethe
boxnongwhichwireiscommonand
whichis“hot.”
4.Splicetheblack(orwhite)wirefromthebiSensorintothecommonwire
connecon.
5.SplicetheredwirefromthebiSensorintothe“hot”wireconnecon.