Specifications

Manual 2100-590C
Page 8 of 67
* 75 degree C Copper wire size
** Maximum time delay fuse or circuit breaker
TABLE 1A
SPECIFICATIONS
W42G, W48G AND W60G MODELS
Models W42G2-A W42G2-B W42G2-C W48G2-A W48G2-B W48G2-C W60G2-A W60G2-B W60G2-C
Electrical Rating - 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506
Minimum Circuit Ampacity 31 23 11 34 25 12 40 28 14
** Delay Fuse or Circuit Breaker Max. 50 35 15 50 35 15 60 40 20
Compressor
Volts 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Rated Load Amps 15.5/17.5 10.2/11.5 4.8 19.3/21.4 13.1/14.5 6.4 21.6/24.7 12.8/14.7 7.8
Branch Circuit Selection Current 19.9 13.1 6.1 21.4 14.5 6.4 26.3 15.6 7.8
Lock Rotor Amps 109 83.1 41 135 98 55 134 110 52
Energy Recovery Ventilator
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps (3-motors) 2.2 2.2 2.2
Fan Motor
Horsepower 1/3 1/3 1/3
Volts 230/208-60-1 460-60-1 230/208-60-1 460-60-1 230/208-60-1 460-60-1
Full Load Amps 2.5 1.3 2.5 1.3 2.5 1.3
CFM 3050 3050 3050
Blower Motor 156 156 156 240 240 240 246 246 246
Horsepower 1/3 1/3 1/3
Volts 230/208-60-1 460-60-1 230/208-60-1 460-60-1 230/208-60-1 460-60-1
Full Load Amps 3.4 1.5 3.4 1.5 3.4 1.5