Specifications
Manual 2100-590C
Page 44 of 67
TABLE 14
W48G INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS
Recommended W48G cooling airflow range at rated 1550 CFM @ .20 ESP (WC) is 1250 - 1780 CFM
Factory set on Medium Speed for cooling and Medium Speed for heating.
Voltage adjustment – Reduce airflow by 130 CFM for 208 Volt
Top outlet adjustment – Increase airflow by 65 CFM for top outlet models
SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 125,000 BTU Input 113,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1520 - - - - - - 1580 1180 - - - 1580 1180
0.2 1710 1450 - - - 1880 1510 - - - - - - 1510 1110
0.3 1600 1400 - - - 1760 1460 - - - - - - 1460 1090
0.4 1480 1290 - - - 1670 1340 - - - 1670 1340 - - -
0.5 1390 - - - - - - 1560 1240 - - - 1560 1240 - - -
0.6 1270 - - - - - - 1430 - - - - - - 1430 1130 - - -
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 100,000 BTU 90,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1560 - - - - - - 1630 1230 - - - 1630 1230
0.2 1760 1490 - - - - - - 1560 1160 - - - 1560 1160
0.3 1630 1440 - - - 1810 1510 1140 - - - 1510 1140
0.4 1530 1330 - - - 1720 1390 - - - 1720 1390 1020
0.5 1440 1210 - - - 1610 1290 - - - 1610 1290 970
0.6 1320 - - - - - - 1480 1180 - - - 1480 1180 - - -
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 75,000 BTU Input 68,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1600 - - - - - - 1680 1280 - - - 1680 1280
0.2 1805 1530 - - - - - - 1610 1210 - - - 1610 1210
0.3 1680 1480 - - - 1860 1560 1190 - - - 1560 1190
0.4 1580 1360 - - - 1770 1440 1070 - - - 1440 1070
0.5 1490 1280 - - - 1660 1340 970 1660 1340 970
0.6 1370 - - - - - - 1530 1230 - - - 1530 1230 - - -










