Specifications

Manual 2100-590C
Page 42 of 67
TABLE 12
W36G INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS
Recommended W36G cooling airflow range at rated 1100 CFM @ 0.250 ESP (WC) is 940 - 1250 CFM
Factory set on Medium Speed for cooling and for heating.
Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt
Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment – Increase airflow by 50 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 90,000 BTU Input 81,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1220 1000 - - - 1260 1060 - - - 1260 1060
0.2 - - - 1160 950 1370 1200 1010 - - - 1200 1010
0.3 1250 1080 - - - 1290 1120 940 - - - 1120 940
0.4 1150 990 - - - 1190 1030 - - - 1190 1030 860
0.5 1050 - - - - - - 1090 950 - - - 1090 950 - - -
0.6 940 - - - - - - 980 - - - - - - 980 840 - - -
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 68,000 BTU Input 61,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1220 1000 - - - 1260 1060 - - - - - - 1060
0.2 - - - 1160 950 - - - 1200 1010 - - - - - - 1010
0.3 1250 1080 - - - - - - 1120 940 - - - 1120 940
0.4 1150 990 - - - 1190 1030 860 - - - 1030 860
0.5 1050 - - - - - - 1090 950 780 1090 950 780
0.6 940 - - - - - - 980 840 - - - 980 840 660
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 45,000 BTU Input 41,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - 1220 1000 - - - 1260 1060 - - - - - - 1060
0.2 - - - 1160 950 - - - 1200 1010 - - - 1200 1010
0.3 1250 1080 - - - 1290 1120 940 - - - 1120 940
0.4 1150 990 - - - 1190 1030 860 - - - 1030 860
0.5 1050 - - - - - - 1090 950 780 1090 950 780
0.6 940 - - - - - - 980 840 660 980 840 660