Specifications

Manual 2100-590C
Page 40 of 67
TABLE 10
W24G INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS
Recommended W24G cooling airflow range at rated 800 CFM @ 0.15 ESP (WC) is 700 - 910 CFM
Factory set on Low Speed for cooling and High for heating.
Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt
Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment – Increase airflow by 50 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 90,000 BTU Input 81,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - - - - 820 1260 1060 - - - - - - 1060 870
0.2 - - - 950 770 1200 1010 - - - 1200 1010 - - -
0.3 - - - 880 700 1120 - - - - - - 1120 940 - - -
0.4 - - - 790 - - - 1030 - - - - - - 1030 860 - - -
0.5 910 710 - - - - - - - - - - - - 950 - - - - - -
0.6 800 - - - - - - - - - - - - - - - 840 - - - - - -
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 68,000 BTU Input 61,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - - - - 820 1260 1060 870 - - - 1060 870
0.2 - - - 950 770 1200 1010 - - - - - - 1010 810
0.3 - - - 880 700 1120 910 - - - 1120 940 - - -
0.4 - - - 790 - - - 1030 - - - - - - 1030 860 - - -
0.5 910 710 - - - 950 - - - - - - 950 780 - - -
0.6 800 - - - - - - - - - - - - - - - 840 - - - - - -
ESP
Inches
H
2
O
COOLING MODE MANUAL FAN and HEATING MODE
Wet Coil 45,000 BTU Input 41,000 BTU Input
High Medium Low High Medium Low High Medium Low
0.1 - - - - - - 820 1260 1060 870 - - - 1060 870
0.2 - - - 950 770 1200 1010 810 1200 1010 810
0.3 - - - 880 700 1120 910 - - - 1120 940 750
0.4 - - - 790 - - - 1030 860 - - - 1030 860 680
0.5 910 710 - - - 950 780 - - - 950 780 - - -
0.6 800 - - - - - - 840 - - - - - - 840 - - - - - -