NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
PATEGNAR
042602352
802781022
17. THERMOSTATS
16. WIRING – LOW VOLTAGE WIRING
Low Voltage Connection
These units use a 24-volt AC low voltage circuit.
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
“G” terminal is the fan input.
“Y1” terminal is the compressor input.
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“A” terminal is the ventilation input. This terminal
energizes any factory or field installed vent option.
“W1” terminal is the heat input.
230/208 VOLT UNITS
All models are equipped with dual primary voltage
transformers. All equipment leaves the factory wired
on 240V tap. For 208V operation, reconnect from
240V to 208V tap. The acceptable operating voltage
range for the 240V and 208V taps are:
460 VOLT UNITS
All models are equipped with single primary voltage
transformers and no rewiring is required.
TABLE 3
THERMOSTAT WIRE SIZE
remrofsnarT
AVALFeguaGeriW
mumixaM
ecnatsiD
teeFnI
553.2eguag02
eguag81
eguag61
eguag41
eguag21
54
06
001
061
052
FIGURE 10
INSTALLATION OF FLEXIBLE CONDUIT
TABLE 4
WALL THERMOSTAT
tatsomrehTserutaeFetanimoderP
750-3048
0401D0113HT
loocegats1,taehegats1
otua-no:naFlooc-ffo-taeh:metsyS
elbammargorP-noNcinortcelE
850-3048
1511D0225HT
taehegats2,loocegats2
elbammargorP-noNcinortcelE
lanoitnevnoCroPH
revoegnahclaunaMrootuA
060-3048
544-0211
taehegats3;loocegats3
cinortcelEelbammargorP-noN/elbammargorP
lanoitnevnoCroPH
revoegnahclaunaMrootuA
Direct Digital Controls (DDC)
For total and proper control using DDC, a total of 5
controlled outputs are required (4 if no ventilation is
installed).
LOW VOLTAGE CONNECTIONS FOR DDC CONTROL
Fan Only Energize G
Cooling Mode Energize G, Y1
Heating Mode Energize W1
Ventilation Energize G, A