2.  1-Stage Compressor Units with Newer   
  ECONWMT Economizers (See Note A)
1
st
 stage cooling set point is the setting (SP) input into 
the controller. Factory default is 77F (25C). On a call 
for cooling the blower of the lead unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 1 LED will blink for 10-seconds before 
going solid, at which time the lead unit Y1 cooling 
output turns on. If the outdoor temperature and 
humidity conditions are below the set point of the 
economizer control the lead unit economizer will 
operate instead of the compressor. If outdoor conditions 
are not acceptable for free cooling the compressor will 
automatically operate instead of the economizer. 
2
nd
 cooling set point is 4F (default setting, user 
selectable 2-6F) warmer than Stage 1. On a call for 
2
nd
 stage cooling the lead unit Y2 cooling output turns 
on. If the outdoor temperature and humidity conditions 
are below the set point of the economizer control the 
lead unit economizer will continue to operate, and the 
compressor will operate. If the compressor is already 
operating on 1
st
 stage cooling because outside free 
cooling range no action occurs at 2
nd
 cooling set point.
3
rd
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 2. On a call for 3
rd
 Stage cooling 
the blower of the lag unit will come on immediately (if 
not already on – See Blower Operation), and the Stage 
3 LED will blink for 10-seconds before going solid, 
at which time the lag unit Y1 cooling output turns on. 
The lag unit economizer will operate if the outdoor 
temperature and humidity conditions are below the set 
point of the economizer control. If outdoor conditions 
are not acceptable for free cooling the compressor will 
automatically operate instead of the economizer. 
4
th
 cooling set point is 2F (default setting, user 
selectable 2-3F) warmer than Stage 3. On a call for 
4
th
 Stage cooling the lag unit Y2 cooling output turns 
on activating the lag unit compressor. If the outdoor 
temperature and humidity conditions are below the set 
point of the economizer control the lag unit economizer 
will continue to operate. If the compressor is already 
operating on 3
rd
 stage cooling because outside free 
cooling range no action occurs at 4
th
 cooling set point.
3.  2-Stage Compressor Units with Newer  
  ECONWMT Economizers (See Note A)
1
st
 stage cooling set point is the setting (SP) input into 
the controller. Factory default is 77F (25C). On a call 
for cooling the blower of the lead unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 1 LED will blink for 10-seconds before 
going solid, at which time the lead unit Y1 cooling 
output turns on. If the outdoor temperature and 
humidity conditions are below the set point of the 
economizer control the lead unit economizer will 
operate instead of the compressor. If outdoor conditions 
are not acceptable for free cooling the compressor will 
automatically operate on compressor Stage 1 partial 
capacity instead of the economizer. 
2
nd
 cooling set point is 4F (default setting, user 
selectable 2-6F) warmer than Stage 1. On a call for 
2
nd
 stage cooling the lead unit Y2 cooling output turns 
on. If the outdoor temperature and humidity conditions 
are below the set point of the economizer control the 
lead unit economizer will continue to operate, and the 
compressor will operate on compressor Stage 1 partial 
capacity. If the compressor is already operating on 
Stage 1 partial capacity because outside free cooling 
range the compressor will switch to compressor Stage 2 
full capacity. 
3
rd
 cooling set point is 2F (default setting, user 
selectable 2-3F) warmer than Stage 2. On a call for 3
rd
Stage cooling the blower of the lag unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 3 LED will blink for 10-seconds before 
going solid, at which time the lag unit Y1 cooling output 
turns on. The lag unit economizer will operate if the 
outdoor temperature and humidity conditions are below 
the set point of the economizer control. If outdoor 
conditions are not acceptable for free cooling the 
compressor will automatically operate on compressor 
Stage 1 partial capacity instead of the economizer. 
4
th
 cooling set point is 2F (default setting, user 
selectable 2-3F) warmer than Stage 3. On a call for 4
th
Stage cooling the lag unit Y2 cooling output turns on 
activating the compressor. If the outdoor temperature 
and humidity conditions are below the set point of 
the economizer control the lag unit economizer will 
continue to operate, and the compressor will operate on 
compressor Stage 2 full capacity. If the compressor is 
already operating on Stage 1 partial capacity because 
outside free cooling range the compressor will switch to 
compressor Stage 2 full capacity.
Note A:  Economizers in ECONWMT-Series are available 
with either “T” temperature only outdoor sensor or “E” 
enthalpy (temperature and humidity) outdoor sensor. The 
“T” versions will have a xed (but selectable) outdoor 
temperature decision whereas on the “E” versions 
the outdoor temperature decision will oat based on 
outdoor humidity and the selected Enthalpy curve in the 
economizer control module.
HEATING SEQUENCE OF OPERATION
Note:  All heating sequences for air conditioners with 
electric heat or heat pumps will automatically operate 
in Alternating Lead/Lag/Lead/Lag sequence even if 
controller is set to Non-Alternating for cooling with or 
without economizers.
1.  Air Conditioners with Electric Heat
1
st
 stage heating set point is the dead-band (db) below 
the 1
st
 stage cooling set point (the SP entered into the 
program). The dead-band is adjustable from 2-40F, and 
factory default is 27F.
2
nd
 stage heating set point will operate at same inter 
stage differential as set for cooling mode.