INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER MODELS P1124A2 P1130A2 P1136A2 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned.
Contents Getting Other Informations and Publications ........ 1 General Instructions ................................................. Important ................................................................ Shipping Damage .................................................... Field-Installed Heater Packages (Optional) .............. 4 4 4 4 Installation ................................................................. 6 Location ................................................................
Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ........................... ANSI/NFPA 70 Standard for the Installation ...................... ANSI/NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air .............................
TABLE 1 ELECTRICAL DATA Q R Rated Volts & Phases S HZ Maximum External Minimum Fuses or Circuit Operating Maximum Ckt. Brk. Ampacity Voltage Unit Range Amps Ckt. A Ckt. A P1124A2 230/208-1 60 197 - 253 12.9 25 17 10 10 P1130A2 230/208-1 60 197 - 253 17.6 30 21 10 10 P1136A2 230/208-1 60 197 - 253 19.4 40 25 8 10 P1136A1-B 230/208-3 60 197 - 253 14.8 25 18 10 10 P1136A1-C 460 60 414 - 506 7.
TABLE 3 OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLE Heater Pkg. Model Unit Volts No. Phase EH3PB-A05 EH3PB-A08 EH3PB-A10 EH3PB-A15 Htr. KW & Capacity @ 240V (or 480V if applicable) KW BT UH Circuit B Htr. KW & Capacity @ 208 Volts KW BT UH @ 240V R Q S or 480V as Heater No. Minimum Maximum Field Ground applicable Internal Field Circuit Overcurrent Power Wire Htr. Amps Fuses Ckts. Ampacity Protection Wiring Size 240/208-1 240/208-1 240/208-1 240/208-1 5 8 10 15 17,100 3.75 27,300 6.0 34,100 7.
GENERAL INSTRUCTIONS IMPORTANT The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
FIGURE 1 PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF ONE PIECE CONSTRUCTION – READY TO INSTALL MIS-1177 CURB AND ROOF DETAILS Roof Curb A 9042-003 80-3/8 B C* D E F J* H* 40-1/4 37-1/4 38-3/8 35-3/8 42 14-3/4 19-1/8 *Duct Sizing Information Return Air Dimension “C” is length Return Air Dimension “H” is width Roof Hood Model Air Conditioning Units RHE36 P1124A2, P1130A2, P1136A2 Supply Air Dimension “C” is length Supply Sir Di
INSTALLATION TABLE 4 LOCATION GENERAL The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings. RATED CFM AND EXTERNAL STATIC PRESSURE (ESP) WET COIL (COOLING) Rated CFM Rated ESP Recommended Air Flow Range P1124A2 800 .
FIGURE 3 ELEVATED MOUNTING PLATFORMS MIS-1183 FIGURE 4 AIRFLOW and SERVICE ACCESS CLEARANCES MIS-1185 Manual 2100-323 Page 7
FIGURE 5 ROOF TOP APPLICATION (May also be required for ground level installations.
5. OTHER INSTALLATIONS – Many other installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any way so as to cause operation difficulties. B. The indoor coil drain pan is equipped with a coupling that must be piped through a condensate drain trap to a suitable drain. C. Always mount the unit is such a position that it may be easily reached for servicing and maintenance. D.
WIRING – MAIN POWER FIGURE 8 – LOW VOLTAGE WIRING Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required.
START UP AND OPERATION THREE PHASE SCROLL COMPRESSOR START UP INFORMATION SEQUENCE OF OPERATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction. compressor contactor starting the compressor and outdoor motor.
SERVICE AND TROUBLESHOOTING SERVICE HINTS FIGURE 9 FAN BLADE SETTING DIMENSIONS 1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs. 2. Check all power fuses or circuit breakers to be sure that they are the correct rating. 3.
FIGURE 10 BRAZING DIAGRAM MIS-1179 TABLE 9 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil Degrees F Model P1124A2 P1130A2 P1136A2 Return Air Pressure Temperature 75 80 85 90 95 100 105 110 115 75 deg. DB 62 deg. WB Low Side High Side 70 219 74 220 77 224 79 234 80 248 82 258 83 276 84 293 85 316 80 deg. DB 67 deg. WB Low Side High Side 75 224 79 225 82 230 84 240 86 254 88 265 89 283 90 300 91 324 85 deg. DB 72 deg.