Product Overview
Note 1: Optional remote 35-foot space temperature sensors available, Bard PN 8612-023A. Controller automatically detects any connected sensors.
Note 2: Multiple Sensor Control Strategy:
A. If only the standard local sensor is used, it will govern space temperature control along with low and high temperature alarm monitoring.
B. If 1 remote sensor is installed and connected, the temperature readout display and the building temperature are controlled to an average of connected sensors.
If there is more than 10F difference between the two sensors, the actual control will be governed by the hottest sensor for cooling and the coldest sensor for heating.
Note 3: Requires optional field installed humidity controller that closes on-rise, Bard PN 8403-038 recommended. Both HVAC unit must be equipped with electric
heat for this sequence to work properly.
Form No. S3548-1116
Supersedes NEW
Page 2 of 8
Feature Selection Guide MC4002 MC4002-A MC4002-AC MC4002-B MC4002-BC
2-unit lead/lag Yes Yes Yes Yes Yes
Cooling stages 4 4 4 4 4
Heating stages (configured for A/C with electric heat) 2 2 2 2 2
Heating stages (configured for Heat Pump) 4 4 4 4 4
Selectable Inter-Stage & On/Off Differentials Yes Yes Yes Yes Yes
Temperature control type Electronic Electronic Electronic Electronic Electronic
Display (4 character .375" high LCD) Digital Digital Digital Digital Digital
Stage “On” LED 4 cool/4 heat 4 cool/4 heat 4 cool/4 heat 4 cool/4 heat 4 cool/4 heat
Lead unit LED Yes Yes Yes Yes Yes
Advance (switch) lead unit feature Yes Yes Yes Yes Yes
One button comfort (72F Cooling, 68F Heating for 1-hour) feature Yes Yes Yes Yes Yes
Local sensor (standard with controller) Yes Yes Yes Yes Yes
Remote sensors option (See Notes 1 and 2) 2 2 2 2 2
Controller locking feature (prevents unauthorized changes) Yes Yes Yes Yes Yes
Smoke/fire lockout circuit (immediate shutdown of controller & A/C) Yes Yes Yes Yes Yes
Generator run feature (inhibits lag A/C unit operation) Yes Yes Yes Yes Yes
Humidity control feature (See Note 3) Yes Yes Yes Yes Yes
Heat pump control feature Yes Yes Yes Yes Yes
Selectable continuous fan control, lead-both-none Yes Yes Yes Yes Yes
Both fans On @ 5F delta T between 2 sensors (selectable) Yes Yes Yes Yes Yes
Control strategy to limit excessive compressor cycling Yes Yes Yes Yes Yes
-24/48Vdc backup power connection for emergency alarms Yes Yes Yes Yes Yes
20-gauge metal controller enclosure Yes Yes Yes Yes Yes
Power loss alarm relay for both units No Yes Yes Yes Yes
HP/LP refrigerant lockout alarm relay for both units No Yes Yes Yes Yes
Smoke/fire alarm relay No Yes Yes Yes Yes
Low temperature alarm thermostat and relay No Yes Yes Yes Yes
High temperature #1 alarm thermostat and relay No Yes Yes Yes Yes
Power loss alarm LED for both units No Yes Yes Yes Yes
HP/LP refrigerant lockout LED for both units No Yes Yes Yes Yes
Smoke/fire LED No Yes Yes Yes Yes
Low temperature alarm LED No Yes Yes Yes Yes
High temperature #1 alarm LED No Yes Yes Yes Yes
Ethernet Communication Board for Remote Connectivity No No Yes No Yes
SNMP (Simple Network Management Protocol) traps and IPV6 No No No No Yes
High temperature #2 alarm relay No No No Yes Yes
2nd stage cooling alarm relay No No No Yes Yes
Controller failure alarm relay No No No Yes Yes
Economizer relay (emergency vent strategy) No No No Yes Yes
High temperature #2 alarm LED No No No Yes Yes
Controller failure alarm LED No No No Yes Yes