Specifications
Manual 2100-549L
Page 5 of 59
TABLE 1
FACTORY BUILT-IN ELECTRIC HEAT TABLE
Models I30H1-A I30H1-B I30H1-C
I36H1-A
I42H1-A
I36H1-B
I42H1-B
I36H1-C
I42H1-C
I48H1-A
I48H1-B
I60H1-B
I48H1-C
I60H1-C
I60H1-A
KW
240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1
BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH
4.0 13,652 10,239
5.0 17,065 12,799 17,065 12,799 17,065 12,799 17,065 12,799
6.0 20,478 15,359 20,478 20,478 15,359 20,478 20,478 15,359 20,478
9.0 30,717 23,038 30,717 30,717 23,038 30,717 30,717 23,038 30,717
10.0 34,130 25,598 34,130 25,598 34,130 25,598 34,130 25,598
15.0 51,195 38,396 51,195 38,396 51,195 51,195 38,396 51,195 38,396 51,195 51,195 38,396
18.0 61,434 46,076 61,434
20.0 68,260 51,195 68,260 51,195
I-TEC Series General Information
I-TEC MODEL NOMENCLATURE
I 36 H 1 D A 0Z R P 4 X X 2
SPECIAL UNITS
(–) – Standard
D – Dehum.
REVISION
VOLTS & PHASE
A – 230/208, 60-1
B – 230/208, 60-3
C – 460-60-3
COIL TREATMENT
X – Std. Hydrophilic Fin Evap. &
Uncoated Alum. Cond. Coil
1 – Phenolic Coated ID Coil
2 – Phenolic Coated OD Coil
3 – Phenolic Coated ID & OD Coil
CONTROLS
X – 24V Terminal Block Only w/o
CompleteStat
1
– CompleteStat THO (Temp,
Humidity & Occupancy)
2
– CompleteStat THO w/CO2
3
– CompleteStat THO w/Ethernet
4
– CompleteStat THO w/CO2 &
Ethernet
MODEL
SERIES
NOMINAL
CAPACITY
30 – 30,000 BTUH
36 – 36,000
42 – 42,000
48 – 48,000
60 – 60,000
ELECTRIC HEAT
0Z – No heat w/breaker
04 – 4KW 1-Phase
05 – 5KW 1-Phase
06 – 6KW 3-Phase
09 – 9KW 3-Phase
10 – 10KW 1-Phase
15 – 15KW 1 & 3-Phase
18 – 18KW 3-Phase
20 – 20KW 1-Phase
VENTILATION OPTIONS
B – Blank-Off Plate
M – Multi-Speed CRV
N – Comb. CRV & DB Economizer
R – ERV
FILTER OPTIONS
P – 2" Pleated MERV 8
M – 2" Pleated MERV 11
N – 2" Pleated MERV 13
COLOR OPTIONS
X – Beige paint
1 – White paint
4 – Gray paint
SYSTEM TYPE
HEAT PUMP
RESERVED
Note: CompleteStat must be field
installed & wired. All units have
24V terminal block.
Motor will deliver consistent CFM through voltage supply range with no deterioration.
Continuous fan CFM is the total air being circulated during continuous fan mode.
Will operate at rated Full Load Airflow when operating with Heat Pump.
Will occur automatically with a call for "W3" or "Emergency Heat" signal from the thermostat (Heat Pump Operation is
terminated at this condition).
TABLE 1A
INDOOR BLOWER PERFORMANCE
MODEL
Rated
ESP
MAX
ESP
Continuous
Airflow
Rated 2nd
Stage CFM
Rated 1st
Stage CFM
5 – 9KW
CFM
13.5 – 18KW
CFM
I30H1 .15 0.50 500 900 650 700 1400
I36H1 .15 0.50 600 1150 850 700 1400
I42H1 .20 0.50 650 1300 950 700 1400
I48H1 .20 0.50 725 1500 1050 700 1400
I60H1 .20 0.50 850 1700 1200 700 1400