TROUBLESHOOTING
FIGURE 11
FAN BLADE SETTING
TABLE 1
FAN BLADE DIMENSION
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efciency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specic situations
can affect the pressure readings, this information should
only be used by certied technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on
each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser
and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
TABLE 2
REFRIGERANT CHARGE
TABLE 3
REFRIGERANT CHARGE
The suction line temperatures in Table 4 above are
based upon 80°F dry bulb / 67°F wet bulb (50% R.H.)
temperature and rated airow across the evaporator
during cooling cycle.
The correct system R-410A charge is shown on the unit
nameplate. Optimum unit performance will occur with
a refrigerant charge resulting in a liquid subcooling as
shown in Tables 2 & 3. If charge is in doubt, reclaim and
recharge to factory nameplate charge.
"A"
AIRFLOW
MIS-1724
Model
Dimension
A
J17A2 / J17L2
J24A2 / J24L2
1.00"
J30A2 / J30L2
J36A2 / J36L2
1.25"
J42A2 / J42L2
J48A2 / J48L2
J60A2 / J60L2
J70A2 / J70L2
1.75"
Model
Rated
Airow
95°F OD
Temperature
82°F OD
Temperature
J24A2 / J24L2 800 56 - 60 56 - 60
J30A2 / J30L2 1000 57 - 61 57 - 61
J36A2 / J36L2 1100 56 - 60 57 - 61
J42A2 / J42L2 1400 58 - 62 60 - 64
J48A2 / J48L2 1550 63 - 67 65 - 69
J60A2 / J60L2 1650 63 - 67 64 - 68
Model
Rated
Airow
95°F OD
Temperature
82°F OD
Temperature
J17A1 / J17L1 550 18 - 21° 19 - 22°
J70A1 / J70L1 1800 15 - 18° 16 - 19°
FAN BLADE SETTING DIMENSIONS
Shown in Figure 11 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 1 for unit specic dimension.
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.