User Guide
Printed in U.S.A. 9-08 © Copyright 2008 TAC All Rights Reserved. F-27197-4
Application
VB-8303 series three-way valves control hot or chilled
water in heating or air conditioning systems. These
valves may be piped as mixing valves with 2 inlets ("A"
and "B") and one outlet ("AB") or as diverting valves
with one inlet ("AB") and two outlets ("A" and "B"). They
are used for two-position or proportional control
applications. Valve assemblies require an
electric/electronic or pneumatic actuator and valve
linkage that may be purchased separately or as part of
a complete factory valve assembly.
These valves will also operate satisfactorily as two-way
angle valves if either end (side) port is closed off.
Danger:
Do not use for combustible gas applications.
The VB-8303 series valves are not rated for
combustible gas applications, and if used in these
applications, gas leaks and explosions may result.
Caution:
Piping must always use the "AB" (bottom)
port as the common. Whether diverting or mixing, the
"AB" port is the common. Pipe accordingly.
Features
• Valve sizes 2-1/2" to 6".
• Excellent close-off capability up to 35 psi.
• Meets ANSI III seat leakage specifications.
• 125 psig pressure rating per ANSI Standards
(B16.1–1993) for flanged cast iron bodies.
• Self-adjusting spring-loaded TFE/EPDM packing.
• Expanded operating temperatures 20° to 281°F
2-1/2" to 6" 125 psi Flanged
Universal Three-Way
Mixing/Diverting Valves
General Instructions
VB-8303 Series
Typical of VB-8303-0-5-P
2-1/2” to 6”