User Guide
4 © Copyright 2008 TAC All Rights Reserved. F-27197-4
Flow Characteristics
When piped as a mixing valve, flow from either of the two inlet ports to the outlet is
approximately linear, which means that the total flow from the outlet is almost constant over
the stroke of the valve stem. See Figure-1 for typical flow characteristics of VB-8303 series
valve bodies.
When piped as a diverting valve, flow from the inlet port to either of the two outlet ports is
approximately linear, which means that the total flow to the inlet is almost constant over the
stroke of the valve stem.
As either port begins to open, it is characterized similar to an equal percentage curve to
enhance system stability.
Table-2 Typical Compatible Actuators and Linkages
Actuator Series Control Signal Type Spring Return
Required Valve Linkage
Normal
Position
2-1/2” to 5"
Valves
6" Valves
MA61-7200 Two Position 120 Vac Yes None
a
—Stem Up
MA61-7201 Two Position 230 Vac Yes None
a
—Stem Up
MA61-7203 Two Position 24 Vac Yes None
a
—Stem Up
MA41-7150 Two Position 120 Vac Yes AV-607 AV-609 Stem Up
b
MA41-7151 Two Position 230 Vac Yes AV-607 AV-609 Stem Up
b
MA41-7153 Two Position 24 Vac Yes AV-607 AV-609 Stem Up
b
MA40-7170 Two Position 120 Vac Yes AV-607 AV-609 Stem Up
b
MA40-7171 Two Position 230 Vac Yes AV-607 AV-609 Stem Up
b
MA40-7173 Two Position 24 Vac Yes AV-607 AV-609 Stem Up
b
MF-63103 Floating 24 Vac No AV-672 — None
MF-63123 Floating 24 Vac
c
No AV-672 — None
MF-63123-211 Proportional Vdc
d
No AV-672 — None
MF-63123-411 Proportional mAdc
e
No AV-672 — None
MF41-6343
Floating 24 Vac
No — AV-609 None
MF41-7153
Yes
AV-607 AV-609 Stem Up
b
MF40-7173
MF61-7203 None
a
—Stem Up
MK-6811
f
Pneumatic 5 to 10 psig
f
Yes AV-497 — Stem Up
MK-6911 with AK-42309-500
g
Pneumatic 5 to 10 psig
g
Yes — AV-497 Stem Up
MS41-7153 Proportional 2 to 10 Vdc
h
Yes AV-607 AV-609 Stem Up
MS40-7170
Proportional 2 to 10 Vdc
h
Yes AV-607 AV-609 Stem Up
b
MS40-7171
MS40-7173
MS41-6340
Proportional 2 to 10 Vdc
h
No — AV-609 NoneMS41-6341
MS41-6343
MS61-7203 Yes None
a
—Stem Up
a
a
Linkage integral to actuator.
b
As shipped from factory. May be field configured for normally stem down.
c
MFC-8000 and MFC-420 plug-in control modules may be field installed for proportional control.
d
MFC-8000 control module factory installed, set for 6 to 9 Vdc, 1” (25 mm) stroke.
e
MFC-420 control module factory installed, set for 4 to 20 mAdc, 1” (25 mm) stroke.
f
AK-42309-500 positive positioner may be ordered separately and field adjusted for other ranges. Order a VK4 valve assembly for factory-installed positive
positioner.
g
AK-42309-500 positive positioner must be used with MK-6911 on 6” VB-8303. Order separately. May be field adjusted for other ranges. Order a VK4 valve
assembly for factory-installed positive positioner.
h
May be field configured for 4-20 mAdc.