Durability of valve stems and packings is dependent on maintaining non-damaging water
conditions. Inadequate water treatment or filtration, not in accordance with chemical
supplier/ASHRAE handbook recommendations, can result in corrosion, scale, and abrasive
particle formation. Scale and particulates can result in stem and packing scratches and can
adversely affect packing life and other parts of the hydronic system.
To maintain non-damaging conditions, follow these guidelines:
• Clean the system prior to start up. Use a nitrite or molybdate-based treatment program.
• Use filtration equipment where needed.
• Properly store off-line systems and monitor water treatment results using corrosion test
coupons.
• Follow the advice of a water treatment professional.
• Consult EN-205, Water System Guidelines Engineering Information, F-26080, for
further details.
DIMENSIONAL DATA
Table-7 Dimensions for VB-7312 Series Valves (Figure-6).
Figure-6 Dimensions for VB-7312 Series Valve Bodies.
Valve Body
Part Number
Valve
Size
Dimensions in Inches (mm)
ABC
D
(Stem Down)
E
(Stroke)
VB-7312-0-4-2
VB-7312-0-4-4
5/8"
O.D.
4
(102)
2-1/4
(57)
1-11/16
(43)
3/4
(19)
7/16
(11)
A
E
C
B
D