Product Overview
Schneider Electric 839 North Perryville Rd. Rockford, IL 61107 1-888-444-1311 www.schneider-electric.com
F-27649-2 September 2013
© 2013 Schneider Electric. All rights reserved.
VB-7200 Two-Way Globe Valve Bodies
Venta
13
Cv Kv
Inlet Pressure (psig)
a
2 psig Inlet 5 psig Inlet 10 psig Inlet 15 psig Inlet 20 psig Inlet 25 psig Inlet
Differential Pressure (psi)
a
Two
Position
Prop.
Two
Position
Prop.
Two
Position
Prop.
Two
Position
Prop.
Two
Position
Prop.
Two
Position
Prop.
0.2 1.6 0.5 4 1 8 1.5 12 2 14 2.5 16
0.1 0.09 0.5 1.5 0.9 2.4 1.5 3.5 2.0 4.4 2.4 5.1 2.9 5.8
0.22 0.2 1.2 3.2 2.0 5.2 3.2 7.6 4.3 10 5.3 11 6.4 13
0.4 0.3 2.2 5.9 3.7 9.5 5.8 14 7.8 17 9.7 20 12 23
0.75 0.6 4.1 11 7.0 18 11 26 15 33 18 38 22 44
1 0.9 5.4 15 9.3 24 15 35 20 44 24 51 29 58
1.3 1.1 7.1 19 12 31 19 45 25 57 32 66 38 76
1.8 1.6 10 27 17 43 26 62 35 79 44 92 52 105
2.2 1.9 12 32 20 52 32 76 43 96 53 112 64 129
2.9 2.5 16 43 27 69 42 101 57 127 70 148 84 169
3.25 2.8 18 48 30 77 47 113 63 142 79 166 94 190
4.4 3.8 24 65 41 105 64 153 86 192 107 225 127 257
5 4.3 27 74 46 119 73 173 98 219 121 255 145 292
5.5 4.8 30 81 51 131 80 191 107 240 133 281 159 321
6.3 5.4 34 93 59 150 92 218 123 275 153 322 182 368
7.5 6.5 41 111 70 178 110 260 146 328 182 383 217 438
8.2 7.1 45 121 76 195 120 284 160 359 199 419 237 479
8.5 7.4 46 125 79 202 124 295 166 372 206 434 246 497
9 7.8 49 133 84 214 131 312 176 393 218 460 260 526
10 8.7 54 147 93 238 146 347 195 437 243 511 289 584
12 10.4 65 177 112 285 175 416 234 525 291 613 347 701
14 12.1 76 206 130 333 204 485 273 612 340 715 405 818
16 13.8 87 236 149 380 234 555 312 700 388 817 463 935
18 15.6 98 265 167 428 263 624 351 787 437 919 521 1052
20 17.3 109 295 186 475 292 694 390 874 485 1021 579 1168
22 19 120 324 204 523 321 763 429 962 534 1124 636 1285
24 20.8 131 354 223 571 351 832
468 1049 582 1226 694 1402
28 24.2 153 413 260 666 409 971 546 1224 679 1430 810 1636
31 26.8 169 457 288 737 453 1075 605 1355 752 1583 897 1811
34 29.4 185 501 316 808 497 1179 663 1487 825 1736 984 1986
40 34.6 218 590 372 951 584 1387 780 1749 970 2043 1157 2337
a. Values are for saturated steam (K = 1). Left column under each inlet pressure is for two position control, and right column is for proportional control.
Always select the correct valve series for the inlet steam pressure as shown below:
Valve Series Max Inlet Pressure for
Saturated Steam
Maximum Media
Temperature
VB-7273-0-4-, VB-7283-0-4-, VB-7275-0-4-, VB-7285-0-4- 150 psi (1034 kPa) 20 to 400°F (-7 to
204°C)
VB-7253-0-4-, VB-7263-0-4-, VB-7255-0-4-, VB-7265-0-4- 100 psi (690 kPa) 20 to 340°F (-7 to
171°C)
VB-7213-0-4-, VB-7223-0-4-, VB-7215-0-4-, VB-7225-0-4-, VB-7212-0-4-, VB-7222-0-4-,
VB-7214-0-4-, VB-7224-0-4-, VB-7211-0-3-, VB-7211-0-4-, VB-7221-0-4-, VB-7251-0-3-,
VB-7211-0-4-
35 psi (240 kPa) 20 to 281°F (-7 to
138°C)
1 Pound per Hour = 0.45359 Kilogram Per Hour
Steam Capacity in Pounds per Hour
F-27649-1.indd 13 3/28/14 1:09 PM