Selection Guide
Schneider Electric    839 North Perryville Rd. Rockford, IL 61107    1-888-444-1311    www.schneider-electric.com
F-27649-2   September 2013
© 2013 Schneider Electric. All rights reserved.
VB-7200 Two-Way Globe Valve Bodies
Venta
8
Valve Sizing and Selection
Sizing for Water 
Two-position
Two-position control valves are normally selected 
“line size” to keep pressure drop at a minimum. If 
it is desirable to reduce the valve below line size, 
then 10% of “available pressure” (that is, the pump 
pressure differential available between supply and 
return mains with design flow at the valve location) is 
normally used to select the valve.
Proportional and Floating
Proportional and floating control valves are usually 
selected to take a pressure drop equal to at least 
50% of the “available pressure.” As “available 
pressure” is often difficult to calculate, the normal 
procedure is to select the valve using a pressure 
drop at least equal to the drop in the coil or other 
load being controlled (except where small booster 
pumps are used) with a minimum recommended 
pressure drop of 5 psi (34 kPa). When the design 
temperature drop is less than 60°F (33°C) for 
conventional heating systems, higher pressure drops 
across the valve are needed for good results.
Do Not Exceed the MAXIMUM Recommended 
Pressure Drop Of the Valve
Conventional Heating System 
Design 
Temperature
Load Drop  
°F (°C)
Recommended 
Pressure Drop 
(% of Available 
Pressure) 
Multiplier on 
Load Drop
60 (33) or more 50% 1x Load Drop
40 (22) 66% 2x Load Drop
20 (11) 75% 3x Load Drop
Actuator must be rated to provide close off pressure. 
Cv (Flow Coefficient) Determination
The valves’ water capacity is based on the following 
formula:
Other forms of this formula are:
These formulas can be used to calculate one of the 
three quantities if the other two are known. 
Flow coefficients (Cv’s) for valve bodies are given on 
pages 2 to 6.
Metric (SI) Units
Kvs is defined as the flow in m3/h with DP = 100 kPa 
(1.0 Bar) with the valve completely open.
Flow is calculated using the following formula:
Pressure drop is calculated using the following form 
of the above formula:
These formulas can be used to calculate one of the 
three quantities if the other two are known.
F-27649-1.indd 8 3/28/14 1:09 PM










