Brochure
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), and Screwed, 
Union Sweat (1/2 to 2 in.) with Hydraulic Actuators
86
© Copyright 2006 TAC. All Rights Reserved. F-27414-1
CAUTION: Avoid condensation which can facilitate corrosion. With 40°F (4°C) water, the maximum allowable ambient dew point 
temperature is 68°F (20°C). Piping insulation must not stop drainage at actuator mounting nut. Do not use Hydraulic Actuators 
with fluid temperatures below 40°F (4°C).
TABLE 7. Flow Pattern.
Part Number Flow Type
Stem Up (SU) (Normal Position) Stem Down (SD) 
Flow Closed Port Flow Closed Port
VB-7313-0-4-P Mixing
B to AB A A to AB B
VB-7314-0-4-P
VB-7323-0-4-P Diverting
B to AB A B to A AB
3-1/4
6-3/4
D
E
C
B
A
MA-521X
MP-5X1X
a
MPR-5X1X
a
MF-5X1X
a
with
VB-7313-0-4-P
VB-7314-0-4-P
VB-7323-0-4-P
a
AV-601 linkage extension (not shown) required for hot water applications. Refer to Table 4.