Brochure
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 
to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic 
Actuators
80
© Copyright 2006 TAC. All Rights Reserved. F-27414-1
TABLE 2B.  2-1/2 to 6 in. Valves, 
select Actuator or Actuator Code 
(XXX) having sufficient close-off for 
the application. If selecting 
Component Parts, select 
 and Positive 
Positioner if required.
Effective Area (Stroke)
100 Sq. In. (1 in.) 100 Sq. In. (2 in.)
Valve Linkage
AV-496 AV-496
Positive Positioner
AK-42309-500 AK-42309-500
Factory Assembly with Positive Positioner
No Yes Yes No Yes Yes
Actuator Code (XXX)
⎯ 802 803 ⎯ 812 813
Actuator 
MK-8801 MK-8811 MK-8821 MK-8901 MK-8911 MK-8921
Spring Range (psig)
3 to 8 5 to 10 8 to 13 3 to 8 5 to 10 8 to 13
ACTUATOR CLOSE-OFF PRESSURE RATING (psi)
a
b
a 
Close-off ratings for mixing valves: (SU = “A”, SD = “B” port). “A” port (SU) ratings equal pressure at port “A” minus pressure at port “B”. “B” port (SD) ratings 
equal pressure at port “B” minus pressure at port “A”. Close-off ratings in the table are true only when the indicated supply air pressure is applied to the actuator.
A change in air pressure at the actuator alters the actual close-off pressure.
b 
Close-off pressure ratings describe only the differential pressure which the actuator can close-off with adequate seating force. Consult valve body spec-
ifications for other limitations.
Supply Air Pressure (psig)
15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20
Stem Position
c
c 
SU ⎯ Stem Up; SD ⎯ Stem Down. Refer to Table 5 for flow pattern, port designations and normal position.
SU SD SD SU SD SD SU SD SD SU SD SD SU SD SD SU SD SD
Valve Assemblies Valve Body P Code
Size
in.
——————————————————
VK4-9313-80X-4-P
d
d 
Factory valve assemblies are only available with positive positioner.
VB-9313-0-4-P
-12 2-1/2 30 125
125
60 91
125
120 30 125
—————————
-13
3
20 90 40 62 90 19 90
—————————
VK4-9313-802-5-P
d
VK4-9313-803-5-P
d
VB-9313-0-5-P
-12 2-1/2 30 125 60 91 120 30 125
—————————
-13 3 20 90 40 62 90 19 90
—————————
-14
4
10 48 89 25 33 73 49 10 48
—————————
VK4-9313-812-5-P
d
VK4-9313-813-5-P
d
VB-9313-0-5-P
-15 5
—————————
5 305615204530 5 30
-16 6
—————————
3 203810133020 3 20
TABLE 3. Optional Input Signal Interface to 
Pneumatic.
Input Signal Type Interface Module Required
Two-Position, SPST (Electric) AL-1XX
Two-Position, SPDT Snap Acting (Electric) AL-1XX
Voltage 2 to 15 Vdc TAC System 8000 CP-8511-XXX
Current Input 4 to 20 mA etc. CP-8511-XXX, CP-8551
Valve 
Linkage