Brochure

3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2
to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic
Actuators
80
© Copyright 2006 TAC. All Rights Reserved. F-27414-1
TABLE 2B. 2-1/2 to 6 in. Valves,
select Actuator or Actuator Code
(XXX) having sufficient close-off for
the application. If selecting
Component Parts, select
and Positive
Positioner if required.
Effective Area (Stroke)
100 Sq. In. (1 in.) 100 Sq. In. (2 in.)
Valve Linkage
AV-496 AV-496
Positive Positioner
AK-42309-500 AK-42309-500
Factory Assembly with Positive Positioner
No Yes Yes No Yes Yes
Actuator Code (XXX)
802 803 812 813
Actuator
MK-8801 MK-8811 MK-8821 MK-8901 MK-8911 MK-8921
Spring Range (psig)
3 to 8 5 to 10 8 to 13 3 to 8 5 to 10 8 to 13
ACTUATOR CLOSE-OFF PRESSURE RATING (psi)
a
b
a
Close-off ratings for mixing valves: (SU = “A”, SD = “B” port). “A” port (SU) ratings equal pressure at port “A” minus pressure at port “B”. “B” port (SD) ratings
equal pressure at port “B” minus pressure at port “A”. Close-off ratings in the table are true only when the indicated supply air pressure is applied to the actuator.
A change in air pressure at the actuator alters the actual close-off pressure.
b
Close-off pressure ratings describe only the differential pressure which the actuator can close-off with adequate seating force. Consult valve body spec-
ifications for other limitations.
Supply Air Pressure (psig)
15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20 15/20 15 20
Stem Position
c
c
SU Stem Up; SD Stem Down. Refer to Table 5 for flow pattern, port designations and normal position.
SU SD SD SU SD SD SU SD SD SU SD SD SU SD SD SU SD SD
Valve Assemblies Valve Body P Code
Size
in.
——————————————————
VK4-9313-80X-4-P
d
d
Factory valve assemblies are only available with positive positioner.
VB-9313-0-4-P
-12 2-1/2 30 125
125
60 91
125
120 30 125
—————————
-13
3
20 90 40 62 90 19 90
—————————
VK4-9313-802-5-P
d
VK4-9313-803-5-P
d
VB-9313-0-5-P
-12 2-1/2 30 125 60 91 120 30 125
—————————
-13 3 20 90 40 62 90 19 90
—————————
-14
4
10 48 89 25 33 73 49 10 48
—————————
VK4-9313-812-5-P
d
VK4-9313-813-5-P
d
VB-9313-0-5-P
-15 5
—————————
5 305615204530 5 30
-16 6
—————————
3 203810133020 3 20
TABLE 3. Optional Input Signal Interface to
Pneumatic.
Input Signal Type Interface Module Required
Two-Position, SPST (Electric) AL-1XX
Two-Position, SPDT Snap Acting (Electric) AL-1XX
Voltage 2 to 15 Vdc TAC System 8000 CP-8511-XXX
Current Input 4 to 20 mA etc. CP-8511-XXX, CP-8551
Valve
Linkage