Brochure

2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with
Hydraulic Actuators
28
© Copyright 2006 TAC. All Rights Reserved. F-27414-1
TABLE 3. Factory Assemblies, select exact Actuator Code (XXX). Any MA-52XX, MF-5X1X, MP-5XXX, MPR-5X1X can be
assembled to 1/2 to 1-1/4 in. valve bodies with the close-off pressure ratings listed in Table 2. Select below listed Hydraulic
Actuators or Actuator Codes (XXX) for factory available assemblies. For applications that factory assemblies are not available,
select actuator, linkage, valve body and field assemble.
TABLE 2. Select Actuator Type or Actuator Code
(XXX) series with correct Input Signal having
sufficient close-off for the application. If selecting
Component Parts, select .
Input Signal
Two-Position Electric Vdc mAdc
Valve Linkage
AV-7600-1
a
a
MP-541X, MPR-561X, MPR-571X, and MPR-581X use AV-7600-1 and AV-601.
Actuator Code (XXX)
2XX 2XX
Actuator
MA-521X
MF-5XXX
MP-5XXX
MPR-571X
MPR-561X
MPR-571X
b
b
135Ω slidewire input.
Factory Available
Valve Assembly
Valve Body P Code Size in.
CLOSE-OFF PRESSURE RATING (psi)
c
c
Close-off rated with pressure at inlet (port A). For kPa multiply C
v
by 6.89.
N.O.
VA-7213-2XX-4-P
VS-7213-XXX-4-P
VB-7213-0-4-P
VB-7214-0-4-P
VB-7253-0-4-P
VB-7273-0-4-P
-1-2-3-4 1/2 130
-5-6 3/4 80
-7-8 1 40
-9 1-1/4 25
-10 1-1/2 60
-11 2 35
N.C.
VA-7223-2XX-4-P
VS
-72
23-XXX-4-P
VB-7223-0-4-P
VB-7224-0-4-P
VB-7263-0-4-P
VB-7283-0-4-P
-1-2-3-4 1/2 200 130
-5-6 3/4 130 80
-7-8 1 50 40
-9 1-1/4 35 25
-10 1-1/2 35 25
-11 2 20 14
Input
Signal
Voltage
Vac 50/60 Hz
VA
Aux.
Switch
Actuator
Part No.
Actuator Code (XXX) for Factory Available Assembly
VA-72X3 VS-72X3 VF-72X3
Two-Position SPST
24
18
No
MA-5213 201 ——
120 MA-5210 211
——
240 MA
-5211 221 ——
2 to 15 Vdc. System 8000,
non-positive positioning,
see Calibration Chart.
24 MP-5213 201
120 MP-5210 211
240 MP-5211 221
2 to 15 Vdc, System 8000,
start 6 Vdc factory set,
adjustable 2 to 12 Vdc, 3
Vdc span, positive
positioning
24 MP-5413
247
a
a
Includes AV-601.
120 MP-5410
244
a
240 MP-5411
245
a
4 to 20 mA positive
positioning
24
18
MPR-5613
267
a
120 MPR-5610
264
a
240 MPR-5611
265
a
Floating SPDT 24 21
MF-5413 ——221
a
MF-5513
223
a
Valve Linkage
MA
-
5200 Series