Brochure

Valve Selection Guide for Three-Way Valves
10
© Copyright 2006 TAC. All Rights Reserved. F-27414-1
HOW TO USE TABLE:
1. Select the vertical column that has a valve body series that meets your requirements.
2. Select the horizontal column with correct type of actuator (Pneumatic or Electric/Electronic) and correct input signal for
Electric/Electronic actuator.
3. The intersection of the two columns shows the pages for complete selection and ordering information.
Valve Application Chilled or Hot Water 300°F Maximum
Chilled or Hot
Water 300°F
Maximum
Chilled or Hot
Water 300°F
Maximum
Chilled or Hot
Water 300°F
Maximum
Valve Body Type
Globe
Flared Flared Screwed Screwed Union Sweat Flanged Screwed Flanged
VB-7312-0-4-P VB-324-0-5-P VB-7313-0-4-P VB-9313-0-4-P VB-7314-0-4-P VB-9313-0-5-P VB-7323-0-4-P VB-9323-0-5-P
Static Pressure Rating
250 psig 250 psig 250 psig 250 psig 250 psig 125 psig 250 psig 125 psig
Sizes Available
5/8 in. O.D.,
SAE 45°
1/2 in. O.D.
Tube
1/2 to 2 in. 2-1/2 & 3 in. 1/2 to 2 in. 2-1/2 to 6 in. 1/2 to 2 in. 2-1/2 to 6 in.
Range of Cv’s
Available
2.2 to 4.4 1.5 2.2 to 41 67 to 91 2.2 to 41 74 to 390 4.4 to 40 75 to 275
Flow Type
Mixing
3-Way Mixing,
Top Port
Normally
Closed, Bottom
Port Normally
Open
Mixing Mixing Mixing Mixing Diverting Diverting
PNEUMATIC ACTUATORS
a
a
Optional inputs available to pneumatic are: SPST, SPDT, slidewire (Series 90), TAC System 8000 (voltage input 2 to 15 Vdc), current input 4 to 20 mA.
These options are shown with the specific valve selected.
Pages
70 to 76 70 to 76 77 to 82 77 to 82 77 to 82 77 to 82 77 to 82 77 to 82
ELECTRIC/ ELECTRONIC ACTUATOR
Input Signals
Pages
Two-Position (SPST)
(Spring Return)
70 to 76 70 to 76 83 to 103 87 to 96 83 to 103 87 to 96 83 to 103 87 to 96
Two-Position (SPDT
Snap Acting) (Non-
Spring Return)
——
87 to 103 87 to 96 87 to 103 87 to 96 87 to 103 87 to 96
TAC System 8000,
Voltage Input 2 to 15
Vdc
70 to 76 70 to 76 83 to 103 87 to 96 83 to 96 87 to 96 83 to 96 87 to 96
Slidewire (Series 90)
——
87 to 103 87 to 96 87 to 103 87 to 96 87 to 103 87 to 96
Current Input
4 to 20 mA etc.
——
Floating Control,
SPDT or Two SPST,
Direct Digital Control
——
Pneumatic to Electric
——
Valve
Selecti
on
Guide
for
Three-
Way
Valves