Brochure
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™
Actuators
F-27414-1 © Copyright 2006 TAC. All Rights Reserved. 161
TABLE 1. Select Valve Body including
P Code (Size, Cv Rating, Port Code).
(Refer to Pages 172 to 175 for Valve Sizing.)
Application
Chilled or Hot Water
Internal Parallel Pipe Thread per ISO 7/1, BS 21,
JIS B0203
Size 15 to 50 mm
Valve Body, Actuator Provides Normal Position VB-7315-0-4-P
Actuator Types Input Signal Factory Available Valve Assemblies
MA40-704X, MA40-707X, MA40-715X, MA40-717X SPST
VA-7315-XXX-4-P
VA-7325-XXX-4-P
MS40-6043, MS40-6083, MS40-6153,
MS40-7043, MS40-7073, MS40-7153,
MS40-7170
2 to 15 Vdc
VS-7315-XXX-4-P
VS-7325-XXX-4-P
MF40-6043, MF40-6083, MF40-6153,
MF40-7043, MF40-7073, MF40-7153,
MF40-7173
Floating SPDT
VF-7315-XXX-4-P
VF-7325-XXX-4-P
NOTE: These charts are color
coded as shown below to assist
valve selection. Note it is possible
to select either a valve assembly or
component parts (actuator, valve
linkage, valve body).
ORDERING EXAMPLES:
1. Valve Assembly:
VP-7315-301-4-10
2. Valve Body:
VB-7315-0-4-10
Actuator: MF40-6043
Linkage:
Valve Body Data less P Code
(Size, Cv Rating, Port Code) or
Valve Assembly less Actuator
Code (XXX) and less P Code
(Size, Cv Rating, Port Code)
P Code (Size, Cv Rating, Port
Code)
Actuator or Actuator Code (XXX)
for Valve Assemblies
Flow Type Mixing
Material
Body
Bronze
Seat
Stem Stainless Steel
Plug Brass
Packing Spring Loaded TFE
Disc None
ANSI Pressure Class
a
(psig) Refer to page 169
a
CAUTION: Solder, tubing and/or pipe schedules must meet or exceed working static pressure requirements.
250 (1724 kPa), up to 400 psig (2758 kPa) below 150°F (66°C
b
)
b
Do not apply the above pressure rating to the piping system.
Allowable Control Media Temp
c
c
CAUTION: Freeze protection required for fluid temperatures below 32°F (0°C).
20 to 300°F (-7 to 149°C)
Allowable Differential Pressure for
Water
psig (kPa)
d
d
Less than 20 psi recommended for quiet service.
35 psi (241)Max. for normal life (Refer to page 172 for cavitation limits)
TO SELECT A PORT CODE (P).
P Code
Valve Size
c
in.
Kvs
-2
e
e
Factory assemblies are not available for two-position application using reduced port valve bodies.
15
1.64
-4
3.28
-6 20
5.62
-8 25
10.38
-9 32
14.70
-10 40
20.76
-11 50
31.14
AV-391
Valve Linkage
3-W
a
Glo
b
Val
v
Scr
e
End
to 8
0
mm
)
with
TAC
Dur
a
e™
Act
u
s