Product Overview
TC-5231 Series, TC-5232, TC-5241 Series
264
DC Ratings for TX-5232 Only.
Specifications
Typical Applications
Figure 1 TC-5231 or TC-5241 Switch Action and Terminal Identification.
Volts
FLA
a
a
FLA — Full Load Amps.
LRA — Locked Rotor Amps.
NIA — Non-Inductive Amps.
PDVA — Pilot Duty VA.
LRA
a
NIA
a
PD VA
a
120 4.6 46 3 57.5
240 2.3 23 0.5 57.5
600 — — — 57.5
Setpoint dial range Dual marked 35 to 60°F (1.7 to 15.5°C). TC-5242: 15 to 55qF (-9.4 to 12.8qC).
Sensing element Vapor pressure type, copper construction.
Response
To lowest temperature sensed by any one-foot section of its element. Altitude causes the control to
operate approximately 1°F colder per 1000 ft. of elevation.
Differential 5 F degrees (3 C degrees) fixed.
Electrical switch Refer to Model Chart.
Ratings Refer to Model Chart.
Connections Coded screw terminals.
Mounting In any position on
any surface not subject to excessive vibration.
Housing
Molded gray PVC plastic cover with a zinc-plated steel main enclosure with a 1/2 in. conduit opening.
TC-5242: painted steel housing.
Environment
Ambient temperature limits
Shipping: -40 to 150qF (-40 to 66qC).
Operating: Must be 5qF (3qC) above setpoint to a maximum of 150qF (66qC) at case.
Thermal sensing element: 300qF (149q
C).
Humidity
Enclosure: 5 to 95% RH, non-condensing.
Thermal sensing element: 0 to 100% RH.
Locations NEMA Type 1.
Dimensions
Case
2-45/64 H x 3-1/2 max. W x 2 max. D in. (69 x 89 x 51 mm). TC-5242: 3-1/4 H x 4 L x 2 D in. (83 x
101 x 51 mm)
Element 3/32 in. O.D. x 20 ft. length (2.4 mm x 6.1 m). TC-5242 1/8 in. O.D. x 20 ft. length. (3.2 mm x 6.1 m).
Agency Listings
UL 873
Underwriters Laboratories Inc. listed (File # E9429 Category Temperature-indicating and Regulating
Equipment).
CSA Certified for use in Canada by Underwriters Laboratorie
s. Canadian standards C22.2 No. 24-93.
General Instructions Refer to F-25911.
AC Supply
Earth Ground
(2)
Indication
Circuit
Fan
Motor
(3)
(1)
1 Terminals (2) and (1) close on temperature drop.
1
Temp
Drop