User Guide
F-18895-6 © Copyright 2008 TAC All Rights Reserved. 3
DUAL BULB SELECTION
On the dual bulb units, indoor and outdoor bulbs are 
determined by the ratio selected (see Table-2). Ratio refers to 
the outdoor air temperature change compared to the water 
temperature change. The dial setpoint is the water 
temperature setpoint when the outdoor temperature is 70°F.
To select ratio, it is necessary to know only: (1) outdoor design 
temperature, (2) maximum water temperature at outdoor 
design temperature, and (3) desired water temperature at 
70°F outdoors. Use Table-3 to determine the required ratio 
based on this information and set the dial per item (3).
Note:
If a 1-1/2:1 ratio is selected, the extra dial supplied 
with the unit must be used.
Example:
 Select ratio for an installation with a -10°F design 
temperature and estimated supply water temperature of 75°F 
at 70°F outdoors and 125°F at -10°F outdoors. From Table-3, 
-10°F for 1-1/2:1 ratio, note by interpolation (70°F to 123°F 
with dial at 70°F, 80°F to 133°F with dial at 80°F) that water 
temperature varies from 75°F to 128°F as outdoor 
temperature drops from 70°F to -10°F.
For this application, the 1-1/2:1 ratio should be selected. The 
extra dial supplied with the unit would be used, and the dial set 
at 75°F.
PRE-INSTALLATION
Inspection
Visually inspect the carton for damage. If damaged, notify the 
appropriate carrier immediately. If undamaged, open the 
carton and visually inspect the device for obvious defects. 
Return damaged or defective products.
Required Installation Items
• Wiring diagram
• Tools (not provided):
Volt-ohm meter
Room temperature thermometer on °F or °C
Appropriate screwdriver(s) for cover, terminals and 
mounting screws
Appropriate drill and drill bit for mounting screws
INSTALLATION
Caution:
1. Installer must be a qualified, experienced technician.
2. Disconnect power supply before installation to prevent 
electrical shock and equipment damage.
3. Make all connections in accordance with the electrical 
wiring diagrams, and in compliance with national and 
local codes. 
Use copper conductors only.
4. Do not exceed ratings of the device.
5. Avoid locations where excessive moisture, corrosive 
fumes or vibrations are present.
Location
Locate the device allowing proper distance to the bulb 
location. The case can be mounted in any position. Refer to 
Figure-2 for case dimensions.
Figure-2 Case Dimensions.
Procedure for Remote Bulb Mounting
Air Bulb Models — Mounting in Return Air Duct
1. Remove cover and provide two holes for #10 round head 
screws using the housing as the template or by using the 
dimensions shown in Figure-2.
2. Partially insert the mounting screws in the screw holes. 
Fit the housing over the screws, slide housing down on 
the screws and tighten the screws.
Air Bulb Models — 
Mounting Outside of Return Air Duct
1. Prepare duct for mounting by cutting hole and providing 
mounting screw holes per Figure-2.
2. Fabricate a cover as shown in Figure-3.
3. Carefully roll bulbs toward back of unit and insert through 
2-1/4" x 2-1/2" (57 mm x 64 mm) hole.
4. Remove cover and attach unit to duct with #10 screws.
5. Attach cover over 2-1/4" x 2-1/2" (57 mm x 64 mm) hole.
Side
Back
Bottom
1-5/64"
2"
2-1/4"
5/16"
13-64"
1-9/16"
7/8"
1/2"
1/4"
3-5/8"
TC-4166 
TC-4266
Only
7"
TC-4166 
TC-4266
Only
4-5/8"
TC-4166 
TC-4266
Only
Hole for 1/2" Conduit
Knockout for 3/4" Conduit
TC-4166
TC-4266
Only
Cut Hole in
Duct 2-1/4" W x
2-1/2" H for
Mounting in
Return Air
1"