User Guide
Printed in U.S.A. 8/08 © Copyright 2008 TAC All Rights Reserved. F-18895-6
APPLICATION
For on-off control of media temperature in ducts, tanks, liquid 
lines, etc.
SPECIFICATIONS
Setpoint Dial Range:  Dial plate is marked as °F on one 
side and °C on the other. See Table-2 for specific ranges.
Sensing Element:  Liquid-filled copper.
Differential:  See Table-2.
Dual Bulb Units:  One bulb senses the controlled media; 
the second bulb senses the outside air temperature. The 
temperature of the controlled media increases as outside air 
temperature decreases.
Ambient Temperature Limits:
Case,
Shipping  -40 to 160°F (-40 to 71°C).
Operating  -40 to 150°F (-40 to 65°C): except return 
air bulb unit, -40 to 140°F (-40 to 60°C).
Bulb,  See Table-2.
Electrical Switch: Snap action SPDT, one per stage.
Ratings,  See Table-1.
Connections: Coded screw terminals.
Cover:  All metal with 1/2" to 3/4" conduit openings.
Case Locations:  NEMA Type 1 indoor only.
Mounting:  Case can be mounted in any position. See 
ACCESSORIES for bulb mounting kits (order separately).
Dimensions:
Case,  4-5/8" high x 2-1/4" wide x 2" deep (117 mm x 57 
mm x 51 mm)
Element and Capillary,  See Table-2.
ACCESSORIES
AT-201 Copper bulb well requires AT-209
AT-203  Stainless steel bulb well requires AT-209
AT-206 Copper bulb well
AT-208  Duct mounting kit
AT-209  Bulb mounting kit
AT-210   Concealed adjustment plate
AT-211  Outside bulb shield
* TC-4115 for TAC System 8000 and applications requiring less than one (1) 
amp. Electrical Rating: 1.0 amp at 24 Vac; 0.25 amp at 24 Vdc.
Table-1 Maximum Electrical Rating
(All units except TC-4115*)
Switch Rating (50/60 
Hz)
24V 120V 240V
Full Load Amps 9.8 9.8 8.0
Locked Rotor Amps 58.8 58.8 48.0
Pilot Duty VA 60 360 360
Non-Inductive Amps (Resistive)
Single Stage 22 22 22
Two Stage 16 16 8.0
Figure-1 Switch Action and Terminal Identification.
N.O.
N.C.
Temp. Drop
N.O. makes ON temperature drop
Low (N.O.)
Low (N.C.)
1st stage cool
Temp. Drop
Common
 Common
High (N.O.)
1st stage Heat
High (N.C.)
Temp. Drop
Typical Two Stage
Typical Single Stage
Common
Low
High
TC-4100 Series, TC-4200
Series
Bulb Thermostats & Return Air Thermostats
General Instructions
Typical
Return Air Bulb
Typical
Sin
g
le Bulb
Typical
Dual Bulb