User Guide
Printed in U.S.A. 8-08 © Copyright 2008 TAC All Rights Reserved. F-12720-8
Application
These thermostats are used primarily on combination
heating and cooling air conditioning units to sense
supply media temperature and reverse the control
action of the room temperature sensing element.
Units are hermetically sealed. TC-2942 is enclosed
type and has 1/2” conduit adapter. Fast responding
bimetal element actuates snap-acting SPDT with silver
contacts. Units are supplied with three color coded 16
gauge leads 3 ft. (914 mm) long.
Dimensions: 2 in. (51 mm) diameter x 1-1/2 in. (38
mm) high.
Table-1 Model Chart.
Options
TC-2931-204 with 10 ft. (3 m) cable and plug (which cannot
be extended) for unit ventilator.
TC-2931-205 with 3 ft. (914 mm) cable (which cannot be
extended) for CP-5341.
Accessories
None.
Pre-Installation
The thermostats are shipped with an attached flange and two
mounting springs for mounting on tubing or pipe up to 1-1/2”
(38 mm).
Before installing the thermostat, inspect the unit for any signs
of damage.
Part
Number
Type
Setpoint
°F (°C)
Differential
°F (°C)
Min. Hot
Water
Temp.
°F (°C)
Max.
Chilled
Water
Temp.
°F (°C)
Switch Ratings (AC Only)
Voltage
(Vac)
FLA
(Amps)
LRA
(Amps)
Pilot Duty
(VA)
TC-2931 Strap-On
Fixed
75 (24)
Approx.
Fixed 15
(8)
Approx.
90 (32) 60 (16)
120
240
5.8
2.9
34.8
17.4
125
TC-2942
Strap-On
Enclosed
a
a. Has 1/2” conduit connector
TC-2931
Open Type
TC-2942
Enclosed Type
TC-2931, TC-2942
Changeover Thermostats, Strap-On Type,
Summer/Winter
General Instructions