F-18783-4 © Copyright 2008 TAC All Rights Reserved. 9
d. Continue moving dial in same direction until high stage switch just clicks (makes to
“B”) and note dial reading at this point.
e. The difference in dial readings, as noted, indicates the differential between stages.
For example, if the high, middle, and low stages click (make to “B”) at 71°F, 77°F,
and 84°F, respectively, then the differential between the high and middle stages is
6°F (77 – 71) and between the middle and low stages is 7°F (84 – 77). Total differ-
ential between the low and high stages is then 13°F (84 – 71).
N O T E
If differential between stages is changed after the instrument is calibrated, the calibration
has to be rechecked to make certain that the change in differential did not affect the calibra-
tion. Recheck calibration point (step 3).