User Guide
2 © Copyright 2006 TAC All Rights Reserved. F-20044-2
*Dial stop pins included to limit control range.
**Off position de-energizes thermostat and fan circuits.
PRE-INSTALLATION
Inspection
Inspect the carton for damage. If damaged, notify the
appropriate carrier immediately. Inspect the device for
obvious damage due to shipping. Return damaged products.
Requirements
• Wiring diagram
• Tools (not provided):
Appropriate screwdriver(s) for cover, terminals and
mounting screw.
Appropriate drill and drill bit for mounting screws
Wire cutters and strippers
Caution:
• Installer must be a qualified, experienced technician.
• Make all connections in accordance with electrical wiring
diagrams, and in compliance with national and local
codes. Use copper conductors only.
• NEMA Type 1 covers are intended for indoor use
primarily to provide a degree of protection against
contact with the enclosed components.
INSTALLATION
Thermostats require upright mounting on a properly flat
surface. Locate thermostat where it will be exposed to
unrestricted circulation of air which represents the average
temperature of the controlled space. Install thermostat in any
normal human environment.
Caution:
Do not locate the thermostat near sources of heat
or cold, such as lamps, motors, sunlight, or concealed ducts
or pipes. Avoid locations where excessive vibration,
moisture, corrosive fumes or vapors are present. NEMA Type
1 covers are intended to provide a degree of protection
against contact with the enclosed equipment.
MOUNTING
1. Pull all wires (use copper wire only).
2. Fasten mounting plate to switch box (Figure 2).
3. Make electrical connections to switch leads and
thermostat terminals. (See Figure 4 for typical wiring
diagram).
4. Hook thermostat on top of mounting plate and swing
down into place.
5. Tighten thermostat mounting screw.
Figure-2 Thermostat Mounting.
Table-1 SPECIFICATIONS.
Part
Number
Company
Identification
Sequenced
Heat & Cool
Applications
Control*
Dial
Range
°F (°C)
Thermal
Differential
°F (°C)
Fan
Switch
Marking
Electrical Ratings
Volts
(AC)
Fan Switch Thermostat Contacts
Full
Load
Amps
Locked
Rotor
Amps
Full
Load
Amps
Locked
Rotor
Amps
Pilot
Duty
(VA)
TC-186 TAC
24 Volt
55-85
(13-29)
2 (1.1)
Heat
2 (1.1)
Neutral
2 (1.1)
Cool
Low-Off**
Med-High
24 6 36 4.4 26
125
TC-186-770 Robertshaw
TC-187 TAC
120 Volt 120 6 36 4.4 26
TC-187-770 Robertshaw
TC-188 TAC
240 Volt 240 3 18 3.0 18
TC-188-770 Robertshaw