Submittal Sheet
5
W
C A U T I O N
• Do not exceed ratings of the device(s).
• The thermostat is not designed for service in any location where condensation may
occur. Avoid locations where excessive moisture, corrosive fumes, or vibration is
present. NEMA Type 1 covers are intended for indoor use primarily to provide a degree
of protection against contact with the enclosed equipment.
• Thermostats with guards that restrict air flow must have heating or cooling anticipation.
Mounting
The thermostat requires upright mounting on a flat vertical surface. Locate the thermostat
where it is exposed to unrestricted circulation of air which represents the average tempera-
ture of the controlled space.
1. Pull all wires from source to thermostat location.
2. Make electrical connection to thermostat (see Figure-2 through Figure-4).
3. Remove thermostat cover and fasten thermostat to box or wall (see Figure-5).
4. Attach thermostat cover (see Figure-5).
CHECKOUT
After installing a thermostat, make an initial check of the switching action. Verify the switch
action by listening to and watching the switch contacts or by using a voltmeter between the
proper sides of the switch.
1. Run the setpoint dial to a temperature above ambient. This should cause the thermostat
to make a circuit between the orange and brown leads.
2. Slowly turn the setpoint dial setting to a lower temperature. This breaks the circuit
between the orange and brown leads. The contact blade is in a neutral position between
the two contacts (not making a circuit to either contact). Turn the setpoint further down
to again lower the temperature. This causes the thermostat to make a circuit between
the orange and red leads.
CALIBRATION
All thermostats are calibrated at the factory and normally do not require any such attention.
However, if recalibration is necessary for any reason, proceed as follows:
W
W A R N I N G
Turn Off control power and power to night depression circuit, where applicable.
1. Set temperature dial 2°F (1°C) below actual stable room temperature, as read from an
accurate thermometer.
2. Remove cover (see Figure-5).
Figure-5 Thermostat Mounting.
Thermostat
Cover Screw
Switch Box
Mounting Plate
Rounded Tab Up
Thermostat Mounting
Screws (2)