Submittal Sheet
2 © Copyright 2008 TAC All Rights Reserved. F-18781-4
SPECIFICATIONS
Sensing Element: Bimetal operated snap action SPDT switch with neutral center.
Differential: 2°F (1°C) on heat, 2°F (1°C) on neutral, 2°F (1°C) on cool.
Connections: Color coded 6" leads.
Cover: Plastic as standard.
Mounting: Flush or surface switch box or directly on wall (24 Vac only).
Dimensions: 4-3/8" high x 2-7/8" wide x 1-5/8" deep (111 mm x 73 mm x 43 mm).
Table-1 Specifications.
*Dial stop pins included to limit dial range.
Table-2 Standard Units Include the Following.
Table-3 Agency Approvals.
*Only available as factory assembly. Do not convert from plastic to metal cover in the field.
Standard Cover
TC-1191
TC-1191-116
TC-1191-770
TC-1191-500 Parallel heating or cooling anticipation, 24 Vac
TC-1191-602 10°F night depression, 24 Vac
Part Number
Company 
Identification
Control* 
Dial Range
Full Load Amps Locked Rotor Amps
Pilot Duty
(VA)
24/120 Vac 240 Vac 24/120 Vac 240 Vac
TC-1191
Barber-
Colman
55 to 85°F
4.4,
Orange to 
Brown Lead
3.0,
Orange to 
Red Lead
2.2,
Orange to 
Brown Lead
1.5,
Orange to 
Red Lead
26.4, 
Orange to 
Brown Lead
18,
Orange to 
Red Lead
13.2, 
Orange to 
Brown Lead
9,
Orange to 
Red Lead
40 @ 24 Vac
210 @
120/240 Vac
TC-1191-116 13 to 29°C
TC-1191-500 55 to 85°F
TC-1191-602 55 to 85°F
TC-1191-770 Robertshaw 55 to 85°F
Quantity Description
1 Blank cover insert
1 Cover insert with setpoint dial cutout
1 5/64" Allen head screw for securing cover to thermostat base
1 5/64" Allen wrench
2 Dial stop pins to limit setpoint range
Configuration Part Number UL Listed CSA Certified
Metal cover option TC2-1191* No Yes
Plastic cover
TC-1191 Yes No
TC-1191-116 Yes No
TC-1191-770 Yes No
Heat anticipation or night 
depression options
TC-1191-500 No No
TC-1191-602 No No
ROBERTSHAW
ROBERTSHAW
ROBERTSHAW
TC-1191
with
Insert Insert
Standard
TC-1191-770
with
Insert Insert
Standard