User Guide

4 © Copyright 2008 TAC All Rights Reserved. F-18785-9
CALIBRATION (See Figure 3)
All thermostats are precision calibrated at the factory and
normally will not require any further attention. However, if
recalibration is necessary, proceed as follows:
1. Turn off control power and power to night depression circuit,
where applicable.
2. Set setpoint dial to correspond to actual stable room
temperature, as read from an accurate thermometer.
3. Remove thermostat cover. Do not breathe on the thermostat
or handle excessively as this will affect the accuracy of the
final calibration.
4. If contact blade is the made to left (red) contact, with a small
screwdriver, turn calibration screw counterclockwise (looking
at head of screw) until blade makes to right (brown) contact.
Note:
Each complete turn of screw changes calibration
approximately 15°F (8°C).
Now turn screw very slowly clockwise until blade just makes
the left (red) contact. Thermostat is now properly calibrated.
If contact blade is originally made to the right (brown) contact,
turn calibration screw slowly clockwise until element just
makes the left (red) contact. Thermostat is now properly cali-
brated.
5. Replace thermostat cover.
6. Connect power to thermostat.
7. Recheck calibration about 30 minutes later to be sure heat
from handling of or breathing on bimetal element did not result
in an erroneous setting.
Figure-3
HEAT ANTICIPATION (See Figures 7 and 8)
Parallel heat anticipation is recommended for :
Systems with excess heating capacity that can cause
objectionable space temperature swings.
Thermostats mounted on walls (i.e., concrete) that change
temperature slowly and/or have insufficient air flow over the
device.
COOLING ANTICIPATION (See Figure 8)
Parallel cooling anticipation is recommended for:
Cooling anticipations where current draw exceeds 1 ampere.
Cooling lockout (self heat of the thermostat causing over
cooling of the space) can occur on these applications.
Systems with excess cooling capacity that can cause
objectionable space temperature swings.
Thermostats mounted on walls (i.e., concrete) that change
temperature slowly and/or have restricted air flow over the
device.
CONCEALED CONTROL DIAL
Knurled Dial Removal (See Figure 4)
1. Remove thermostat cover.
2. Secure the control dial with hand so that the dial will not rotate.
3. Place needle nose pliers at knurled ring of the control dial at
the points where the knurled ring is attached to the control
dial.
4. Twist the pliers at each knurled ring attachment point until the
entire knurled ring of the control dial is removed.
Figure-4 Knurled Dial Removal.
LIMIT CONTROL DIAL RANGE
Dial Stop Pin Insertion (See Figure 5)
1. Remove thermostat cover.
2. Secure the control dial with hand so that the dial will not rotate.
3. Place a dial stop pin in the jaws of a needle nose pliers.
4. Insert the dial stop pin in the appropriate hold on either (or
both) side(s) of the control dial to restrict dial rotation.