User Guide

Printed in U.S.A. 8/08 © Copyright 2008 TAC All Rights Reserved. F-18785-9
APPLICATION
For low or line voltage on-off control of fan coils, fans
motor starters, contactors, two-position electric
actuators.
SPECIFICATIONS:
Setpoint Dial Range: See Table 1.
Sensing Element: Bimetal.
Differential: 2°F (1°C).
Electrical Switch: Snap action SPDT.
Rating: See Table 3.
Connections: Color coded 6" leads.
Cover: Beige plastic as standard and brushed bronze cover
insert.
Location: NEMA Type 1 indoor only.
Mounting: Flush or surface 2 x 4 switch box or directly to
wall (24 volt only).
Dimensions: 4-3/8 Hx 2-7/8 W x 1-5/8 D in.
(111 x 73 x 41 mm).
Anticipators: Anticipators are recommended for all
thermostats mounted on concrete walls, or other wall
surfaces that change temperature slowly or have reduced
response time to changes in space temperature. Response
time is further reduced for thermostats with guards that
restrict air flow over the thermostat. Anticipators are
recommended on thermostats that are subjected to restricted
air flow conditions and in small spaces for human occupancy,
e.g., hotel guest rooms and offices.
Standard Models Include (Company identification
shown on cover and inserts.)
One (1) Blank cover insert
One (1) Cover insert with setpoint dial output
One (1) 5/64
" Allen head screw for securing cover to
thermostat base
One (1) 5/64
" Allen wrench
Two (2) Dial stop pins to limit setpoint range
Two (2) Mounting screws
Options for TAC only (for quantities of 24 or more each
part number)
Add *dash-number* (-XXX) suffix to base part number
for desired option. For metal covers, specify
TC2-110X-XXX. All models include dial stop pins to
limit setpoint range.
TC-1101, TC-1102 & TC-1103
Series
Two-Position, Electric Room Thermostats
General Instructions
Full Dial Cover Shown
(Covers must be ordered
separately except as noted.)