User Guide

Table Of Contents
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-13893-7
SPECIFICATIONS
Actuator Inputs
Compatible With: Proportional pneumatic signal. See Table-1.
Start Point, Non-adjustable.
Air Connections: 1/8" FNPT located on side of housing.
Actuator Outputs
Mechanical:
Stroke, 1/2" (12.6 mm) nominal.
Environment
Ambient Temperature Limits:
Shipping, -40 to 220° F (-40 to 104° C).
Operating, -20 to 220° F (-29 to 104° C).
Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 1 indoor only.
Maximum Air Pressure: 30 psig (207 kPa).
Spring: Retracts actuator shaft and raises valve stem on loss of air pressure.
Springs provided in AV-400 linkage (order separately).
Table-1 Spring Ranges.
ACCESSORIES
AK-42309-500 Positive positioner and linkage;
use with MK-2690-0-0-1 or MK-2690-0-0-2 models only
AV-400 Valve linkage
TOOLS
TOOL-95-1 Pneumatic calibration tool kit
MAINTENANCE PARTS
PNV-102 Diaphragm
Actuator
Part Number
Nominal Spring Range*
(Spring Color Code)
psig kPa
MK-2690
3 to 7 (Yellow) 21 to 48
5 to 10 (Black) 34 to 69
8 to 13 (Blue) 55 to 90
*Nominal (no load) condition, spring ranges based on 1/2" (13 mm) maximum stroke, provided by AV-400 linkage