Selection Guide

6 © Copyright 2009 TAC. All rights reserved. F-27470-3
AV-801/AV-802 — Actuator, Linkage, and Close-off Information for 1/2” and 3/4” Two- and
Three-way Johnson Controls Valves with TAC Spring Return Actuators
Note: Do not use TAC Forta actuators with Johnson Controls 1/2” and 3/4” VG7xxxxx and VTM-xxxxx valve bodies (insufficient
valve stroke).
AV-803 — Actuator, Linkage, and Close-off Information for 1/2” and 3/4” Two- and
Three-way Johnson Controls Valves with TAC Spring Return Actuators
For three-way valves, use the lowest published close-off pressure (normally open or normally closed) for the
actuator selected.
Note: Do not use TAC Forta actuators with Johnson Controls 1/2” and 3/4” VG7xxxxx valve bodies (insufficient valve stroke).
Johnson
Controls
Valve
Models
Actuator MK-2690 Mx51-710x
Additional Linkage AV-7400 Included
a
a
Linkage included in actuator.
Valve Stroke 5/16”
b
b
Pneumatically-actuated valves with less than 1/2” stroke may require you to adjust the throttling range of the controller to obtain good proportional control.
5/16”
b
5/16”
b
5/16”
Spring Range 3-7 psig 5-10 psig 8-13 psig
VG7xxxxx
VTM-xxxxx
1
/
2
” Normally Open 220
c
c
20 psig supply air pressure.
170
c
90
c
250
3
/
4
” Normally Open 130
c
120
c
60
c
200
1
/
2
” Normally Closed
Not
Recommended
50 130 250
3
/
4
” Normally Closed 30 60 200
Johnson
Controls
Valve
Models
Actuator MK-2690 Mx51-710x
Additional Linkage AV-7400
a
a
No separate linkage required.
Valve Stroke 5/16”
b
b
Pneumatically-actuated valves with less than 1/2” stroke may require you to adjust the throttling range of the controller to obtain good proportional control.
5/16”
b
5/16”
b
5/16”
Spring Range 3-7 psig 5-10 psig 8-13 psig
VG7xxxxx
1
/
2
” Normally Open 220
c
c
20 psig supply air pressure.
170
c
90
c
250
3
/
4
” Normally Open 130
c
120
c
60
c
200
1
/
2
” Normally Closed
Not Recommended
50 130 250
3
/
4
” Normally Closed 30 60 200