Selection Guide

12 © Copyright 2009 TAC. All rights reserved. F-27470-3
AV-814 — Actuator, Linkage, and Close-Off Information for Two- and Three-Way Siemens
Valves (TAC Forta Non-Spring Return Actuators)
Note: AV-814 Adapter not required on Mxx00A Models. Tall TAC Forta actuators mount directly on Siemens 599 Series valves.
AV-815 — Actuator, Linkage, and Close-Off Information for Two- and Three-Way Siemens
Valves (TAC Pneumatic and DuraDrive Spring Return Actuators)
For three-way valves, use the lowest published close-off pressure (normally open or normally closed) for the
actuator selected.
Siemens
Valve
Models
Actuator M400A (-VB)
a
a
AV-814 Adapter not required on Mxx00A Models. Tall TAC Forta actuators mount directly
on Siemens 599 Series valves.
M800A (-VB)
a
M1500A (-VB)
a
Valve Stroke 3/4”
599-03xxx
2xx-03xxx
1/2” 250 250
Not
Recommended
3/4” 198 250
1” 92 207
1-1/4” 56 130
1-1/2” 37 88 177
2” 19 48 98
Siemens
Valve
Models
Actuator MK-2690 MK-4601 MK-4611 MK-4621 Mx51-710x Mx51-720x
Additional Linkage AV-7400 AV-401 Included
a
a
Linkage included in actuator.
Included
a
Valve Stroke 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
Spring Range 3-7 psig 5-10 psig 8-13 psig 3-6 psig 5-10 psig 10-13 psig
658-00xx
658-01xx
1/2” Normally Open 220
b
b
20 psig supply air pressure.
170
b
90
b
250
b
250
b
200
b
250 250
3/4” Normally Open 130
b
120
b
60
b
250
b
180
b
120
b
200 250
1” Normally Open 70
b
50
b
25
b
150
b
100
b
65
b
150 200
1-1/4” Normally Open 40
b
30
b
15
b
90
b
60
b
40
b
90 150
1/2” Normally Closed
Not Rec-
ommend
ed
50 130 30 100 250 250 250
3/4” Normally Closed 30 60 20 70 160 200 250
1” Normally Closed 9 30
Not Rec-
ommende
d
30 60 90 200
1-1/4” Normally Closed
Not Rec-
ommende
d
15 15 40 60 150