Submittal Sheet

2 ¤Copyright 2010 Schneider Electric All Rights Reserved. F-27170-6
Applicable Literature
SPECIFICATIONS
Actuator Inputs
Control Signal: See Table-1 thru 4 for actuator models and control types.
Power Input: See Table-1 thru 4. All 24 Vac circuits are Class 2. All circuits 30 Vac and
above are Class 1.
Connections: 3 ft (91 cm) appliance or plenum cables, enclosure accepts 1/2" (13 mm)
conduit connector. For M20 Metric conduit, use AM-756 adaptor.
Actuator Outputs
Electrical:
Position Feedback Voltage (proportional or floating only),
For voltage ranges, the feedback signal is the same range as the input signal. The 4
to 20 mA current range and floating actuators have a 2 to 10 Vdc feedback signal. The
feedback signal can supply up to 0.5 mA to operate up to four additional slave
actuators.
Mechanical:
Timing, See Figure-1 to Figure-4.
Travel, 93° nominal.
Manual Override, Allows positioning of damper or valve using manual crank.
RA/DA Jumper, Permits reverse acting/direct acting control (MS4D models only).
Environment:
Ambient Temperature Limits,
Shipping & Storage, -40 to 160 °F (-40 to 71 °C).
Operating, -22 to 140 °F (-30 to 60 °C).
Humidity: 15 to 95% RH, non-condensing.
Location: NEMA 1. NEMA 2, UL Type 2 (IEC IP54) with customer supplied water tight
conduit connectors. Enclosure is air plenum rated.
Agency Listings
UL 873: Underwriters Laboratories (File #E9429 Category Temperature-Indicating and
Regulating Equipment).
CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards
C22.2 No. 24-93.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
This product fits in Installation Category (Overvoltage Category) II per EN 61010-1.
Australia: This product meets requirements to bear the C-Tick Mark according to the terms
specified by the Communications Authority under the Radiocommunications Act 1992.
Note: All performance specifications are nominal and conform to acceptable industry
standards. For applications at conditions beyond these specifications, consult Schneider
Electric. Schneider Electric shall not be liable for damages resulting from misapplication or
misuse of its products.
F-Number Description Audience Purpose
F-25097 Accessory AM-714 General Instructions
Application Engineers
Installers
Sales Personnel
Service Personnel
Start-up Technicians
Provides step-by-step installation
procedures.
F-26080 EN-205 Water System Guidelines
Describes Schneider Electric approved
water treatment practices.
F-26895
Accessories AM-703, AM-704, AM-705, AM-706,
AM-708 General Instructions
Provides step-by-step installation
procedures.
F-26899 Accessory AM-756 General Instructions
F-27086
Vx-2x13-5xx-9-xx Series, VB-2x13-500-9-xx Series
Schneider Electric DuraLynx™ Ball Valve Assemblies
Ball Valve Body/LInkage Selection Guide
Provides features, specifications,
mounting dimensions, and other criteria
useful in the selection of ball valve
assemblies.