Submittal Sheet

10 ¤Copyright 2010 Schneider Electric All Rights Reserved. F-27170-6
MANUAL OVERRIDE OPERATION
When necessary, the actuator’s output shaft can be repositioned using the manual override
mechanism (Figure-10) as follows:
1. Disconnect power from the actuator. Spring return models will fully return to their normal
position. Non-spring return models will remain in position.
2. Insert the crank in the product. Without pushing in on the crank, rotate the manual
override crank in the direction shown by the arrow on the product label until the actuator
rotates to the desired position. Push in until the mechanism locks in position. Non-spring
return models do not have the locking feature.
3. If you desire to reposition a spring return actuator manually from a locked position, turn
crank 1/8 turn counterclockwise and pull out to release. Adjust position as desired.
4. If you desire to reposition a non-spring return actuator manually, turn the crank in either
direction as needed until you reach the desired position.
Caution:
Only use manual override when the actuator drive motor is not powered.
Engaging the manual override when the actuator is powered will cause damage to the
gears.
Using power tools to adjust the override will cause damage to the gears.
Avoid manually repositioning the actuator beyond its adjustable travel limit setting.
Damper Mounting Mx4D-xxxx-xxx Schneider Electric DuraDrive Series Rotary Damper
Installation
Caution: Do not drill additional holes in the actuator body. Pre-drilled holes are located on
gear plate side to accept #8-32 thread-forming screws for mounting accessories.
Note: The Mx4D-xxxx-xxx rotary actuators mount on shafts up to 1/2” diameter. Two set
screws secure the actuator to the shaft.
Shaft Rotates
Clockwise
To Open
Shaft Rotates
Counterclockwise
To Open
This step determines
shaft rotation. Linkage
may change damper direction.
Min. 2-3/8" (60 mm)
Move the damper to its normal position. Verify the controller action is set to match the
damper application.
Spring return models can be mounted from top or bottom. When mounting from the
top, use AM-772 bracket. See Figure-12.
Normally closed damper: when damper is closed, actuator position indicator should
be at 0°. When damper is open, actuator position indicator should be at 90°.
Normally opened damper: when damper is open, actuator position indicator should
be at 0°. When damper is closed, actuator position indicator should be at 90°.
Figure-11 Rotary Damper Position.