User Guide

F-26645-7 © Copyright 2008 TAC All Rights Reserved. 5
MS40-7043-XXX
AM-709 Damper Position Indicator
AM-710 Universal Clamp for up to 3/4" diameter shafts
AM-711 Crankarm for up to 1/2" round shaft
AM-712 Crankarm Adaptor Kit
AM-713 Mounting Bracket for Honeywell Mod IV, M6415 type actuators, and new installations
AM-715 Crankarm Adaptor Kit for Honeywell Mod IV M6415 type actuators, and new
installations
AM-717 Replacement Universal Clamp
Table-2 Auxiliary Power Supply.
TYPICAL APPLICATIONS (wiring diagrams)
Figure-1 and Figure-2 illustrate typical wiring diagrams for spring return proportional
actuators. See Table-1 for model selection and control signal specifications.
Caution:
This product contains a half-wave rectifier power supply and must not be
powered off transformers used to power other devices utilizing non-isolated full-wave
rectifier power supplies. Refer to
EN-206, Guidelines for Powering Multiple Devices from a
Common Transformer, F-26363
for detailed information.
Note:
DC operation is applicable to models manufactured after date code 0212.
Model # Rating
MS40-7043-MP or MS40-7043-MP5 + 20 Vdc, 25 mA Maximum
Control Wires Blue (+) Grey (-)