User Guide

22 © Copyright 2008 TAC All Rights Reserved. F-26645-7
Rotation Limitation Rotation Limitation for MS40-7043 Series
The Stop Block is used in conjunction with the tab on the universal clamp or the AM-709
position indicator. In order to function properly, the clamp or indicator must be mounted
correctly.
The Stop Block controls the rotational output of the MS40-7043 and MF40-7043-501
actuators. It is used in applications where a damper has a designed rotation that is less than
90°, for example with a 45° or 60° rotating damper. It can also be used to provide a minimum
damper position which is easily set, or changed, without removing the actuator from the
damper.
1. Determine the amount of damper rotation required. The actuator stop block provides
limited rotation from 40° to 95°.
2. Loosen the screw securing the stop block to the actuator.
Note:
The actuator is shipped with the Stop Block mounted to the “L” side. If the damper
application requires the “R” side face the installer, simply remove the Stop Block and screw
and move it to the new location.
3. Slide the stop block into position, so that its edge lines up with the degree graduation
on the actuator face which corresponds with the required rotation. See Figure-5.
4. Secure the stop block in place.
5. Test the damper rotation by applying power and the required control signal. Re-adjust
if necessary.
0
.2
R
.4
.6
.8
1
0
.2
R
.4
.6
.8
1
0
.2
L
.4
.6
.8
1
Figure-5 Adjusting Stop Block for Limited Rotation.