Product Overview

8 © Copyright 2008 TAC All Rights Reserved. F-24788-5
3. Make the required connections. Refer to Figure-1 or Figure-2 for a wiring diagram of your particular application.
4. Slip the conduit onto the base, over the ribs. Refer to Figure-7 and Figure-8.
5. Install the cover plate with two screws. The cover plate and two screws are supplied with the actuator.
6. If flexible conduit is to be installed on both sides of the actuator, repeat the preceding steps to install the second conduit.
Base
Knockout
Figure-6 Removal of Knockout on Actuator Base.
Ribs
Cover Plate
Base
or
Figure-7 Flexible Conduit Installation to Either Side of Actuator.
Transformer
(AM-610 shown)
4 x 4
Conduit
Box
Cover Plate
Leave Knockout in place
Line voltage motor leads when connected
to circuits other than Class 2.
Low voltage control leads may
be connected to a Class 2
circuit if routed separately
from line voltage circuit wiring.
Note: Class 2 circuit wiring must be routed
separately from wiring of other circuits. Do not
route Class 2 circuit wiring in the same conduit
box with the line voltage transformer.
Typical for 24 Vac
models (MP-54X3)
Figure-8 MP-5400 Series Wiring with Separation for Class 2 and Line Voltage Circuits.