Product Overview
4 © Copyright 2008 TAC All Rights Reserved. F-24788-5
TYPICAL APPLICATIONS (wiring diagrams)
Red
Yellow
Blue
Red (+20)
Yellow (OP1)
Blue (COM)
Red
Yellow
Blue
Typical Controllers
CP-8102
TP-810X
TP-8121
TP-8124
TP-8232
24 Vac Black/Blue
120 Vac White
240 Vac White/Black
Green
MP-54xx
MP-54xx
To 4 additional Actuators
Tape off Red lead
Do not connect +20
Vac Power
Green
Vac Power
Black
Figure-1 Typical Control Wiring for Up to Six MP-5400 Series Actuators to
Controllers Requiring External 20 Vdc Power from the Actuator.
Yellow
Red
Yellow
Blue
Red
Blue
OP1
COM
Typical Controllers
CC-8111
CC-8118
CC-8218
CP-8161
CP-8261
24 Vac Black/Blue
120 Vac White
240 Vac White/Black
To 4 additional Actuators
Green
MP-54XX
MP-54XX
Vac Power
Green
Vac Power
Black
Tape off Red lead
Do not connect +20
Tape off
Red lead
Do not
connect +20
Note 1: When applied with most DDC controllers, the
actuatorÕs 20 Vdc supply (red to blue) is not required.
Note 2: When this actuator is used with a DDC controller, it is
important to program the controller's output to provide a
minimum control span of 4.5 to 11.5 Vdc, to assure full
travel to each end of the actuator stroke.
SH
Yellow
Blue
To Controller
AO
COM
Typical DDC
Controllers
MICROZONE¨ II
LCMª
DMS
Yellow
Blue
Figure-2 Typical Control Wiring for Up to Six MP-5400 Series Actuators to
Controllers that Do Not Require 20 Vdc Power from the Actuator.