Product Overview
F-24788-5 © Copyright 2008 TAC All Rights Reserved. 3
Table-3 Maximum Allowable Ambient Air Temperature for Valve Actuators.
ACCESSORIES
Common
11-1612 1/2" conduit bushing
AM-610 Transformer, nipple-mounted, 120/208/240 Vac 50/60 Hz 40 VA (for mounting on conduit box)
Damper Only
AM-111 Crank arm for 5/16" diameter damper shaft
AM-112 Crank arm for 3/8" diameter damper shaft
AM-113 Crank arm for 1/2" diameter damper shaft
AM-115 Crank arm for 7/16" diameter damper shaft
AM-122 Linkage connector straight type
AM-123 Damper clip
AM-125 5/16" diameter x 20" damper rod
AM-125-048 5/16" diameter x 48" damper rod
AM-132 Ball joint connector
AM-161-3 Damper linkage kit
AM-601 Device includes mounting bracket, damper linkage with spring, and AM-122 straight connector. Required to modify (MP-
521X series) valve actuators into 2" (51 mm) stroke damper actuators.
Valve Only
AV-600 Valve linkage
AV-601 Valve linkage extension for hot water and steam applications; use with AV-600
Tools
TOOL-12 Wrench for adjustment of auxiliary switch
TOOL-19 Spring compression tool for AV-600
TOOL-37 1-5/8" open-end wrench
TOOL-202 Manual positioner
Temperature of Media
in the Valve Body
(Check the Rating of the Valve)
°F (°C)
Maximum Allowable Ambient Air Temperature
of MP-54XX Series
AV-600 (Only for
Chilled Water
Applications)
°F (°C)
AV-600 and AV-601
°F (°C)
366 (180)
Do Not Use
88 (31)
340 (171) 93 (34)
281 (138) 103 (39)
181 (83) 120 (48)
80 (26) 140 (60) 140 (60)
a
a Maximum allowable ambient temperature of the actuator, minimum -20° F (-29° C).