Product Overview

2 © Copyright 2008 TAC All Rights Reserved. F-24788-5
SPECIFICATIONS
Actuator Inputs
Compatible with: 2 to 15 Vdc from TAC System 8000, TAC NETWORK 8000, or TAC DMS DDC controllers.
Operating Span, Approximately 3 Vdc fixed.
Start Point, Approximately 6 Vdc fixed.
Impedance, 10,000 Ω or greater.
Power Input: Refer to Table-1 and Table-2.
Connections: Color-coded 4' (1.2 m) leads.
Actuator Outputs
Internal Power Supply, 20 Vdc, 25 mA.
Stroke:
Damper, Approximately 2" (51 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully extended) input range (includes AM-
601 linkage).
Valve, Approximately 9/16" (14.3 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully extended) input range.
Torque: Refer to Table-1 and Table-2.
Nominal Damper Area, Actuator selection should be made in accordance with the damper manufacturer’s specifications.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 140° F (-40 to 60° C).
Operating, -20 to 140° °F (-29 to 60° C).
Damper -20 to 140° °F (-29 to 60° C).
Valve Refer to Table-3.
Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 1.
Agency Listings:
UL 873, Underwriters Laboratories (File #E9429 Category Temperature Indicating and Regulating Equipment).
CSA, Canadian Standards Association (File #LR3728).
European Community, EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
Table-1 Model Chart for Damper Actuators.
Table-2 Model Chart for Valve Actuators. Also for Damper Actuators with Field Assembled Damper Linkages.
Part Number
Actuator Power Input
Positive
Positioner
a
Timing in Seconds @ 72° F (22° C)
Torque Rating
(Extend & Retract)
lb.-in. (N-m)
AC
Voltage
+10/-15%
Hz VA Watts
No Load Stroke
Retract on
Power Loss
To Extend To Retract
MP-5430 120
50 60 18 10 Yes 60 30 15 15 (1.69)
MP-5433 24
a Internal feedback circuitry provides positive positioning of the damper in relation to the controller signal.
Part Number
Actuator Power Input
Positive
Positioner
a
Timing in Seconds @ 72° F (22° C) Required Linkage
AC
Voltage
+10/-15%
Hz VA Watts
No Load Stroke
Retract on
Power Loss
Damper Valve
To Extend To Retract
MP-5410 120
50 60 18 10 Yes 60 30 15 AM-601
b
AV-600
AV-601
c
MP-5411 240
MP-5413 24
a Internal feedback circuitry provides positive positioning of the valve stem in relation to the controller signal.
b With the installation of the AM-601 damper linkage, these valve actuators become functionally the same as the damper actuators listed in Table-1. Refer to
Table-1 for the torque rating.
c May be required for steam and hot water. Refer to Table-3.