Product Overview

F-24789-7 © Copyright 2008 TAC All Rights Reserved. 3
Table-2 Model Chart for Valve Actuators. Also for Damper Actuators with Field Assembled Damper Linkages.
Table-3 Maximum Allowable Ambient Air Temperature for Valve Actuators.
ACCESSORIES
Common
11-1612 1/2" conduit bushing.
AD-8969-612 Capacitor kit For MP-52xx-xxx-0-3 and earlier models only. Capacitor built into MP-
52xx-xxx-0-4 and later models.
Damper Only
AD-553 Sequencing adaptor.
AE-249 Transformer.
AM-111 Crank arm for 5/16" diameter damper shaft.
AM-112 Crank arm for 3/8" diameter damper shaft.
AM-113 Crank arm for 1/2" diameter damper shaft.
AM-115 Crank arm for 7/16" diameter damper shaft.
AM-122 Linkage connector straight type.
AM-123 Damper clip.
AM-125 5/16" diameter x 20" damper rod.
AM-125-048 5/16" diameter x 48" damper rod.
AM-132 Ball joint connector.
AM-161-3 Damper linkage kit.
AM-601 Device includes mounting bracket, damper linkage with spring, and AM-122
straight connector. Required to modify (MP-521x series) valve actuators into 2" (51
mm) stroke damper actuators.
AM-602 Spacer.
Valve Only
AV-600 Valve linkage.
AV-601 Valve linkage extension for hot water and steam applications; use with AV-600
(may be used on chilled water to avoid condensation).
TOOLS
(factory available)
TOOL-12 Wrench for adjustment of auxiliary switch.
TOOL-19 Spring compression tool for AV-600.
TOOL-37 1-5/8" open-end wrench.
TOOL-202 Manual positioner.
Part Number
Actuator Power Input
10
Amps
a
Aux
Switch
a
Common of switch is in series with AC power supply to the motor. Therefore, the switch must be wired to control the same voltage as the actuator itself.
Timing in Seconds @ 72° F (22°
C)
Required Linkage
AC
Voltage ±
10%
60 Hz 50 HZ No Load Stroke Retract
on
Power
Loss
Damper Valve
Watts Amps Watts Amps
To
Extend
To Retract
MP-5210
120 11.7 0.16 12.9 0.19
No
60 40 15 AM-601
b
b
With the installation of the AM-601 damper linkage, these valve actuators become functionally the same as the damper actuators listed in Table-1. Refer to
Table-1 for the torque rating.
AV-7600-1
AV-601
c
c
AV-601 required for steam applications, recommended for hot water applications and in chilled water applications where condensation may occur on actuator.
MP-5210-500 Yes
MP-5211
240 11.8 0.08 13.0 0.09
No
MP-5211-500 Yes
MP-5213
24 12.0 0.80 13.2 0.97
No
MP-5213-500 Yes
Temperature of Media
in the Valve Body
(Check the Rating of the Valve)
°F (°C)
Maximum Allowable Ambient Air Temperature
of MP-52xx Series
AV-600 Only for Chilled
Water Applications
°F (°C)
AV-600 with AV-601 extension
°F (°C)
366 (180) 90 (32) 90 (32)
340 (171) 100 (38) 100 (38)
281 (138) 115 (46) 140 (60)
181 (83) 140 (60) 140 (60)
80 (26) 140 (60) 140 (60)