User Guide
6 Copyright 2008 TAC All Rights Reserved. F-24789-7
Yellow
Red
Yellow
Blue
Orange
N.C.
N.O.
COM
(wired internally to
black power lead)
Brown
Red
Blue
24 Vac Black/Blue
120 Vac White
240 Vac White/Black
MP-52XX-500 models
include internal SPDT
auxiliary switch.
To 4
additional
Actuators
Green
MP-52XX
MP-52XX
Vac Power
Green
Vac Power
Red
Blue
Black
Red
Blue
Max. of 5 additional
MP-52XX. Each
requires one
AD-8969-612 filter.
Capacitor AD-8969-612 must
be connected between Red and
Blue leads (max. 4) MP-52XX.
OP1
COM
Typical Controllers
CC-8111
CC-8118
CC-8218
CP-8161
CP-8261
Note 1: When applied with most DDC
controllers, the actuator’s 20 Vdc
supply (red to blue) is not
required. In such a case, each
actuator requires the installation
of one AD-8969-612 capacitor kit
(filter) between its +20 Vdc (red)
and COM (blue) leads.
Note 2: When this actuator is used with a
DDC controller, it is important to
program the controller's output to
provide a minimum control span
of 4.5 to 11.5 Vdc, to assure full
travel to each end of the actuator
stroke.
SH
Yellow
Blue
To Controller
AO
COM
Typical DDC
Controllers
MICROZONE® II
LCM™
DMS
Yellow
Blue
Required only for MP-52XX-XXX-0-3 and
earlier models. Capacitor built into
MP-52XX-XXX-0-4 and later models.
1
1
1
Figure-3 Typical Control Wiring For Up to Six MP-5200 Series Actuators to
Controllers That Do Not Require 20 Vdc Power From the Actuator.